Process data handling in the event of error

Received invalid process data is not used. The inverter uses the last valid process data received. You can optionally set that the contents of the process data in the inverter are set to the value "0" after invalid process data has been received.
 
The setting in 0x24E5:001 is independent of the response selected in 0x2859:005 if invalid process data has been received!
If the application requires that the drive keeps moving with the last valid process data when receiving invalid process data, set the response "No response" or "Warning" in 0x2859:005. In addition, the selection "Clear data [1]" must not be set in 0x24E5:001. Deleting the process data would stop the motor.
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x24E5:001
Process data handling in case of error: Behavior
Selection which process data the inverter is to use after receiving invalid process data.
0
Keep last data
The last valid process data of the master are used.
1
Clear data
The contents of the process data in the inverter is set to the value "0".
2
Reset control word  
The RUN command is reset. All other parameters keep their current value. All control words linked via the PDO mappings are set to 0.