IO-Link
IO-Link is a registered trademark. It may only be used by members of the IO-Link community and non-members that have purchased the corresponding license. Detailed information on the usage can be found in the IO-Link Community Rules:
io-link.com
io-link.com
IO-Link is the standardized IO technology (IEC 61131-9) for communication with sensors and actuators. Point-to-point communication is based on the three-wire sensor and actuator connection without additional requirements concerning the cable material.
IO-Link is no fieldbus but the further development of the existing connection technology for sensors and actuators.
Preconditions
The control unit (CU) of the inverter is provided with IO-Link.
Scheme of the IO-Link architecture
|
Device
|
Explanation
|
Meaning in the IO-Link network
|
|
PLC
|
Connection from the IO-Link master to the fieldbus level (PLC). Any Ethernet-based fieldbus can be used.
|
-
|
|
IO-Link master
|
Gateway to the fieldbus level, connection point for all IO-Link devices in this specific network. Some support 4 IO-Link devices, others 8 or 16 devices.
|
All brands are possible and compatible (class A plug is required).
|
|
IO-Link device
|
Examples: Sensors, RFID readers, valves, motor starters or I/O modules.
|
Specific IO-Link hardware, control unit for the IO-Link protocol
|
Basic components
IO-Link consists of the following basic components:
–
IO-Link master
–
IO-Link device (e.g. sensors, RFID readers, valves, motor starters, I/O modules).
–
Unshielded 3-wire or 5-wire standard cables.
–
Engineering tool for configuring and parameterizing the IO-Link device.
The IO-Link master establishes the connection between the IO-Link device and the automation system. As a component of an I/O system, the IO-Link master is installed either in the control cabinet or directly in the field as remote I/O in degree of protection IP 65/67.
The IO-Link master communicates over various fieldbuses. An IO-Link master can have several IO-Link ports (channels). A IO-Link device can be connected to each port (point-to-point communication).
In principle, any combination of IO-Link masters and IO-Link devices is possible.
If IO-Link devices different IO-Link specifications are combined, the following must be noted:
–
IO-Link V1.0 and V1.1 devices with the IODD version V1.0 can be operated on an IO-Link master according to V1.0.
–
IO-Link devices according to V1.0 and V1.1 can be operated on an IO-Link master according to V1.1.
–
The most important extensions of version 1.1 are:
–
Parameterization "Data Storage" function
–
Data transfer rate 230.4 kbaud
–
Process data width per port up to 32 bytes
–
Automatic verification of the compatibility in case of replacement
Transmission types
The transmission is divided into three types.
–
Process data: Cyclic data
–
The process data of the IO-Link device is transmitted cyclically and the process data size is also determined by the IO-Link device. Depending on the device process, data from 0 to 12 bytes are possible (for both, input and output).
–
IO-Link device data (parameter): Acyclic data
–
IO-Link device data can be parameters, identification data and diagnostic information. They are exchanged acyclically and at the request of the IO-Link master. IO-Link device data can be written to the IO-Link device and read from the IO-Link device.
–
Events: Acyclic data
–
In case of an event, the IO-Link device signals the occurrence of the event to the IO-Link master. The master then reads out the event. Events can be error messages (e.g. short circuit) and warnings or maintenance data (e.g. contamination, overheating). Error messages are transferred from the IO-Link device via the IO-Link master to the controller or HMI. The IO-Link master can also transfer events and conditions of the IO-Link device. Events include, for example, cable break or communication errors. The transmission of IO-Link device parameters or events takes place independently of the cyclic transmission of the process data. Transmissions do not influence or impair each other.
Transmission rate of the IO-Link protocol
Three transmission rates are specified for the IO-Link modus:
–
COM 1 - 4.8 kBaud
–
COM 2 - 38.4 kBaud
–
COM 3 - 230.4 kBaud
The IO-Link master supports all three data transmission rates and adapts itself automatically to the transmission rate of the IO-Link device. The i550 supports COM 3 (230.4 kBaud)
If transmissions fail, the message is repeated two more times. Only after the failure of the third attempt will the IO-Link master detect a communication failure and will signal it to the higher-level controller.
Typical topology
|
Tree
|
|
|
|
M
|
Master
|
D
|
Device
|