Monitoring

The parameters for setting network monitoring functions are described below.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2859:002
IO-Link monitoring: Data exchange exited
–
From version 05.04
 
Data exchange interrupted (wire breakage, loose connector, or similar).
0
No response
1
Warning
2
Trouble
3
Fault
0x2859:005
IO-Link monitoring: Invalid process data
–
From version 05.04
 
Cyclic data is invalid or no data is received. The error response can be set.
0
No response
1
Warning
2
Trouble
3
Fault