Acyclic data transfer
All parameters from the device description are available via this IO-Link channel. It is always possible to configure the entire function set of the IO-Link device via this channel.
IO-Link device parameter (data objects on request)
IO-Link device parameters are transmitted acyclically upon request of the IO-Link master. The IO-Link master always first sends a request to the IO-Link devicewhich is acknowledged by the IO-Link device. This procedure is the same both for "writing" and "reading".
Address range
There is a parameter address offset between the IO-Link and the Lenze parameter indices (according to the IO-Link specification).
|
IO-Link parameter range from
|
IO-Link parameter range to
|
Index offset
|
Subindex offset
|
Lenze parameter range from
|
Lenze parameter range to
|
|
0x1000
|
0x1FFF
|
0x3000
|
0
|
0x4000
|
0x4FFF
|
|
0x2000
|
0x2FFF
|
0x0000
|
0
|
0x2000
|
0x2FFF
|
|
0x3000
|
0x3FFF
|
0x3000
|
0
|
0x6000
|
0x6FFF
|
Subindex restriction
In IO-Link, an index (parameter with all subindices) must not exceed 232 bytes.
The following indices are too high: 0x2000 and 0x2006.
In IO-Link, each subindex of these parameters is represented by a separate index:
|
IO-Link index
|
IO-Link subindex
|
Lenze OBD index
|
Lenze OBD subindex
|
|
0x201
|
0x0
|
0x2000
|
0x1
|
|
...
|
...
|
...
|
...
|
|
0x211
|
0x0
|
0x2000
|
0x11 (17)
|
|
0x301
|
0x0
|
0x2006
|
0x1
|
|
...
|
...
|
...
|
...
|
|
0x325
|
0x0
|
0x2006
|
0x25 (37)
|