Process data transfer
The process data is used to control the inverter.
–
The process data is transmitted automatically and cyclically between the IO-Link master and the IO-Link device.
–
To be able to optimize the process data transfer to the current application, the total PDO data length can optionally be configured to 6 bytes or 12 bytes. Two different IODD's ("IO-Link Device Descriptions") are available for this purpose.
–
Output data direction: From IO-Link master to IO-Link device.
–
Input data direction: From IO-Link device to IO-Link master.
Changeover of the PDO data length to be transmitted
The changeover can be automatic or manual:
–
Automatic (IO-Link master setting "Type compatible"):
If a device ID other than the one configured in the IO-Link master is detected in the inverter when the IO-Link master starts up, the IO-Link master forces this device ID in the inverter (provided this device ID is compatible with the inverter). The inverter then automatically changes to the corresponding PDO data length.
If a device ID other than the one configured in the IO-Link master is detected in the inverter when the IO-Link master starts up, the IO-Link master forces this device ID in the inverter (provided this device ID is compatible with the inverter). The inverter then automatically changes to the corresponding PDO data length.
–
Manually:
The PDO data length can also be changed manually by rewriting the device ID in 0x2310:009 via the "EASY Starter" engineering tool or directly via IO-Link:
To apply the changed PDO data length:
The PDO data length can also be changed manually by rewriting the device ID in 0x2310:009 via the "EASY Starter" engineering tool or directly via IO-Link:
1.
Save parameter settings: 0x2022:003 (P700.03) = "On / start [1]".
2.
Switch the inverter off and then on again in order that the changed communication settings can get effective.
Afterwards, the mapping can be set via the following parameters:
–
Selection of PDO set: 0x231D
–
Internal mapping of the process input data: 0x24E0:001 ... 0x24E0:012
–
Internal mapping of the process output data: 0x24E1:001 ... 0x24E1:012
Regardless of the number of mapped parameters, the fixed length of the process data for the corresponding device ID is always transferred (excess data is ignored).
Parameter