Process data transfer

The process data is used to control the inverter.
–
The process data is transmitted automatically and cyclically between the IO-Link master and the IO-Link device.
 
–
To be able to optimize the process data transfer to the current application, the total PDO data length can optionally be configured to 6 bytes or 12 bytes. Two different IODD's ("IO-Link Device Descriptions") are available for this purpose.
 
–
Output data direction: From IO-Link master to IO-Link device.
 
–
Input data direction: From IO-Link device to IO-Link master.
 
 
Changeover of the PDO data length to be transmitted
The changeover can be automatic or manual:
–
Automatic (IO-Link master setting "Type compatible"):
If a device ID other than the one configured in the IO-Link master is detected in the inverter when the IO-Link master starts up, the IO-Link master forces this device ID in the inverter (provided this device ID is compatible with the inverter). The inverter then automatically changes to the corresponding PDO data length.
 
–
Manually:
The PDO data length can also be changed manually by rewriting the device ID in 0x2310:009 via the "EASY Starter" engineering tool or directly via IO-Link:
 
–
12 Bytes PDO data length: Set 0x2310:009 = "1"
 
–
6 Bytes PDO data length: Set 0x2310:009 = "3"
 
To apply the changed PDO data length:
 
1.
Save parameter settings: 0x2022:003 (P700.03) = "On / start [1]".
 
2.
Switch the inverter off and then on again in order that the changed communication settings can get effective.
 
 
 
Afterwards, the mapping can be set via the following parameters:
–
Selection of PDO set: 0x231D
 
–
Internal mapping of the process input data: 0x24E0:001 ... 0x24E0:012
 
–
Internal mapping of the process output data: 0x24E1:001 ... 0x24E1:012
 
Regardless of the number of mapped parameters, the fixed length of the process data for the corresponding device ID is always transferred (excess data is ignored).
 
Parameter
Address
Name / setting range / [default setting]
Information
0x231C:001
Process data: Last valid input data
–
Read only
 
–
From version 05.04
 
Last valid process data on the IO-Link communication channel.
0x231C:002
Process data: Last valid output data
–
Read only
 
–
From version 05.04
 
0x231D
PDO set selection
–
From version 05.04
 
Display of the process data selection.
0
PDO set 0 (generic)
Generic data assignment set. Is used if the PDO configuration differs from the default selection (change via controller or engineering tool).
1
PDO set 1 - 12 byte
Standard mapping for 12 byte data transmission
–
Corresponds to Device ID "1 (0x2310:009)
 
3
PDO set 3 - 6 byte
Standard mapping for 6 byte data transmission
–
Corresponds to Device ID "3 (0x2310:009)