PROFIBUS

PROFIBUS® (Process Field Bus) is a widely-used fieldbus system for the automation of machines and production plants.
 
–
PROFIBUS® is a registered trademark and patented technology licensed by the PROFIBUS & PROFINET International (PI) user organisation.
 
–
Detailed information on PROFIBUS can be found on the web page of the PROFIBUS & PROFINET International (PI) user organisation: www.profibus.com
 
–
Information about the dimensioning of a PROFIBUS network can be found in the configuration document for the inverter.
 
 
Preconditions
–
The control unit (CU) of the inverter is provided with PROFIBUS.
 
–
The DIP switch for the node address is set correctly, see: Basic setting and options 
 
–
The device description file of the inverter is imported into the configuration software for the control.
 
 
Device description files for Lenze products can be found on the Internet:
www.Lenze.com 
à
Downloads
à
Product-related Application Knowledge Base articles
 
 
Details
The inverter is integrated into a PROFIBUS-DP network as slave. It is only allowed to receive and acknowledge messages and to respond to requests by a master. The master is also referred to as an active bus node. Two different types are distinguished:
–
Class 1 DP master: central control (PLC or PC) which cyclically exchanges process data with the slave. Acyclic data exchange via a separate transmission channel is also possible.
 
–
Class 2 DP master: engineering, configuration, or operator device (HMI) which only exchanges data with the slave acyclically, e.g. for the purposes of configuration, maintenance, or diagnostics. 
 
 
Communication protocols (PROFIBUS DP)
PROFIBUS DP-V2 is not supported by the inverter.
 
Functions of the communication protocol PROFIBUS DP:
–
DP-V0: cyclic data exchange, diagnostics (all devices).
 
–
DP-V1: acyclic data exchange, process alarm processing (process automation). Note: The inverter does not support any alarm diagnostics.
 
–
DP-V2: cycle synchronisation and time stamp, slave-to-slave communication.
 
A class 1 DP master connection (DPV1 C1) between a cyclic master and slave is established automatically when the "Data Exchange" state has been established. In byte 7 of the parameterisation frame, the "DPV1_Enable" bit must be set. Furthermore, a class 2 DP master connection (DPV1 C2) with the slave can be defined by another master connected. This connection must be established via the "MSAC2_Initiate" service.
The inverter supports the following acyclic DPV1 services:
–
MSAC1_Read/Write: C1 read/write request for a data block.
 
–
MSAC2_Initiate/Abort: connection or disconnection for acyclic data exchange between a class 2 DP master and the slave.
 
–
MSAC2_Read/Write: C2 read/write request for a data block.
 
 
Communication time
The communication time is the time between the start of a request and the arrival of the corresponding response.
The communication times in the PROFIBUS network depend on the ...
–
processing time in the inverter
 
–
Telegram runtime (baud rate/telegram length),
 
–
nesting depth of the network.
 
In the case of the inverter, the processing time for process data is approx. 2 ... 3 ms, and for parameter data (DPV1) it is approx. 10 ms. There are no interdependencies between parameter data and process data.
 
Typical topology
Line with repeater
M
Master
X
Repeater
D
Device (Slave)
R
Activated bus terminating resistor