Example: Selective control of several motors with one inverter
A typical application for the parameter change-over is an application/machine in which several axes must be triggered successively but a simultaneous operation of several motors is not required. In this case, one and the same inverter can trigger the motors in succession. Advantages of this solution are the reduced amount of components (inverters) and a reduced energy consumption.
Principle:
–
The motor to be currently controlled is connected to the inverter via motor contactors. (The contactor system can, for instance, be controlled via the digital outputs of the inverter.)
–
At the same time, the motor and control settings suitable for motor are activated in the inverter by means of parameter change-over.
|
|
|
|
□
|
Motor data change-over (via the "parameter change-over" function)
|
|
□
|
Motor change-over (e.g. via motor contactors)
|
The following table lists all parameters that require different settings for the four motors:
|
#
|
Parameter
|
Name
|
Setting
|
|||
|
M1
|
M2
|
M3
|
M4
|
|||
|
1
|
V/f characteristic shape
|
Linear [0]
|
Square-law [1]
|
Linear [0]
|
Linear [0]
|
|
|
2
|
Base frequency
|
60 Hz
|
60 Hz
|
60 Hz
|
50 Hz
|
|
|
3
|
Maximum utilisation [60 s]
|
150 %
|
120 %
|
150 %
|
150 %
|
|
|
4
|
Fixed boost
|
2.5 %
|
0.0 %
|
4.0 %
|
2.0 %
|
|
|
5
|
Rated speed
|
1745
|
3450
|
1450
|
1450
|
|
|
6
|
Rated frequency
|
60.0 Hz
|
60.0 Hz
|
60.0 Hz
|
50.0 Hz
|
|
|
7
|
Rated power
|
0.75 kW
|
0.75 kW
|
0.75 kW
|
1.50 kW
|
|
|
8
|
Rated voltage
|
480 V
|
480 V
|
480 V
|
400 V
|
|
|
9
|
Rated motor current
|
2,200 A
|
2,100 A
|
2,200 A
|
3,500 A
|
|
|
10
|
Max. current
|
200.0 %
|
150.0 %
|
200.0 %
|
200.0 %
|
|
Settings required for the "parameter change-over" function
The easiest way to make the required settings is via the parameterization dialog in the »EASY Starter«:
1.
Click the button to first select the 10 relevant parameters.
2.
Set values for motor M1 ... M4 in the corresponding fields:
In case of a direct setting in the parameters of the "parameter change-over" function:
–
The addresses must be set in the following: 0xiiiiss00 (iiii = hexadecimal index, ss = hexadecimal subindex)
–
The values for the motors must be set as integer values. The integer value results from the multiplication of the actual setting value by the factor of the respective parameter. In the table of attributes, the factor for each parameter must be given.
The following table shows the required settings:
|
#
|
Address
0x4041:x
|
Name
|
Value 1
0x4042:x
|
Value 2
0x4043:x
|
Value 3
0x4044:x
|
Value 4
0x4045:x
|
|
|
hex
|
decimal
|
||||||
|
1
|
0x2B000000
|
721420288
|
V/f characteristic shape
|
0
|
1
|
0
|
0
|
|
2
|
0x2B010200
|
721486336
|
Base frequency
|
60
|
60
|
60
|
50
|
|
3
|
0x2D4B0100
|
759890176
|
Maximum utilisation [60 s]
|
150
|
120
|
150
|
150
|
|
4
|
0x2B120100
|
722600192
|
Fixed boost
|
25
|
0
|
40
|
20
|
|
5
|
0x2C010400
|
738264064
|
Rated speed
|
1745
|
3450
|
1450
|
1450
|
|
6
|
0x2C010500
|
738264320
|
Rated frequency
|
600
|
600
|
600
|
500
|
|
7
|
0x2C010600
|
738264576
|
Rated power
|
75
|
75
|
75
|
150
|
|
8
|
0x2C010700
|
738264832
|
Rated voltage
|
480
|
480
|
480
|
400
|
|
9
|
0x60750000
|
1618280448
|
Rated motor current
|
2200
|
2100
|
2200
|
3500
|
|
10
|
0x60730000
|
1618149376
|
Max. current
|
2000
|
1500
|
2000
|
2000
|
button to first select the 10 relevant parameters.