Example: Selective control of several motors with one inverter

A typical application for the parameter change-over is an application/machine in which several axes must be triggered successively but a simultaneous operation of several motors is not required. In this case, one and the same inverter can trigger the motors in succession. Advantages of this solution are the reduced amount of components (inverters) and a reduced energy consumption.
Principle:
–
The motor to be currently controlled is connected to the inverter via motor contactors. (The contactor system can, for instance, be controlled via the digital outputs of the inverter.)
 
–
At the same time, the motor and control settings suitable for motor are activated in the inverter by means of parameter change-over.  
 
□
Motor data change-over (via the "parameter change-over" function)
□
Motor change-over (e.g. via motor contactors)
The following table lists all parameters that require different settings for the four motors:
#
Parameter
Name
Setting
M1
M2
M3
M4
1
V/f characteristic shape
Linear [0]
Square-law [1]
Linear [0]
Linear [0]
2
Base frequency
60 Hz
60 Hz
60 Hz
50 Hz
3
Maximum utilisation [60 s]
150 %
120 %
150 %
150 %
4
Fixed boost
2.5 %
0.0 %
4.0 %
2.0 %
5
Rated speed
1745
3450
1450
1450
6
Rated frequency
60.0 Hz
60.0 Hz
60.0 Hz
50.0 Hz
7
Rated power
0.75 kW
0.75 kW
0.75 kW
1.50 kW
8
Rated voltage
480 V
480 V
480 V
400 V
9
Rated motor current
2,200 A
2,100 A
2,200 A
3,500 A
10
Max. current
200.0 %
150.0 %
200.0 %
200.0 %
 
Settings required for the "parameter change-over" function
The easiest way to make the required settings is via the parameterization dialog in the »EASY Starter«:
1.
Click the button to first select the 10 relevant parameters.
 
2.
Set values for motor M1 ... M4 in the corresponding fields:
 
In case of a direct setting in the parameters of the "parameter change-over" function:
–
The addresses must be set in the following: 0xiiiiss00 (iiii = hexadecimal index, ss = hexadecimal subindex)
 
–
The values for the motors must be set as integer values. The integer value results from the multiplication of the actual setting value by the factor of the respective parameter. In the table of attributes, the factor for each parameter must be given.
 
The following table shows the required settings:
#
Address
0x4041:x
Name
Value 1
0x4042:x
Value 2
0x4043:x
Value 3
0x4044:x
Value 4
0x4045:x
hex
decimal
1
0x2B000000
721420288
V/f characteristic shape
0
1
0
0
2
0x2B010200
721486336
Base frequency
60
60
60
50
3
0x2D4B0100
759890176
Maximum utilisation [60 s]
150
120
150
150
4
0x2B120100
722600192
Fixed boost
25
0
40
20
5
0x2C010400
738264064
Rated speed
1745
3450
1450
1450
6
0x2C010500
738264320
Rated frequency
600
600
600
500
7
0x2C010600
738264576
Rated power
75
75
75
150
8
0x2C010700
738264832
Rated voltage
480
480
480
400
9
0x60750000
1618280448
Rated motor current
2200
2100
2200
3500
10
0x60730000
1618149376
Max. current
2000
1500
2000
2000