Information on the network

The following parameters show information on the network.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2382:001
Active PROFINET settings: IP address
–
Read only
 
Display of the active IP address.
0x2382:002
Active PROFINET settings: Subnet
–
Read only
 
Display of the active subnet mask.
0x2382:003
Active PROFINET settings: Gateway
–
Read only
 
Display of the gateway address.
0x2382:004
Active PROFINET settings: Station name
–
Read only
 
Display of the active station name.
0x2382:005
Active PROFINET settings: MAC Address
–
Read only
 
Display of the active MAC address.
0x2388
PROFINET status
–
Read only
 
Bit coded display of the current Bus status.
Bit 0
Initialized
The network component is initialised.
Bit 1
Online
After initialisation, the network component waits for a communication partner and the system power-up.
Bit 2
Connected
The network component has established a cyclic I/O communication relationship to a communication partner.
Bit 8
PROFINET stack ok
0x2389:001
PROFINET error: Error 1
–
Read only
 
The parameter currently contains the error detected on the network.
–
The error values may occur in combination with the error values from parameter 0x2389:002.
 
0
No error
0x2389:002
PROFINET error: Error 2
–
Read only
 
The parameter currently contains the error detected on the network.
–
The error values may occur in combination with the error values from parameter 0x2389:001.
 
Bit 7
IP address error
The IP address is invalid. Valid IP addresses are defined according to RFC 3330.
Bit 8
Station name problem
The station name must be assigned according to the PROFINET specification.
Bit 9
DataExch left
PROFINET communication is continuously interrupted in the "Data_Exchange" state, e. g. by cable break.
–
PROFINET communication changes to the "No_Data_Exchange" state.
 
–
When the watchdog monitoring time specified by the IO Controller has elapsed, the response set in is triggered in the device.
 
Bit 14
Initialization problem
The stack cannot be initiated with the user specifications. A reason might be, e. g., a station name that does not correspond to the PROFINET specification.