Supported operating modes

Details
In the following, the steps required for configuring the operating mode "CiA: Velocity mode (vl)" are described.
1.
Set the operating mode "CiA: Velocity mode (vl) [2]" in 0x6060.
 
2.
Set speed is specified via the parameter "Set speed" 0x6042.
 
3.
Process input data and process output data are available for the control in the CiA402.
 
The following signal flow shows the internal setpoint logics:
The "CiA: Velocity mode (vl)" operating mode is now active and the inverter reacts to the setpoint speed specified via the network.
 
The inverter only supports the CiA 402 operating mode "CiA: Velocity mode (vl)".
 
Parameter
Address
Name / setting range / [default setting]
Information
0x6060
CiA: Operation mode
–
Setting can only be changed if the inverter is disabled.
 
CiA: Operation mode
-3
MS: Position mode
-2
MS: Velocity mode
Vendor specific velocity mode
-1
MS: Torque mode
Vendor specific torque mode
–
Only possible in motor control type 0x2C00 = "Sensorless vector control (SLVC) [4]" or "Servo control (SC ASM) [2]".
 
0
No selection
No selection
2
CiA: Velocity mode (vl)
CiA: Velocity mode
0x6061
CiA: Active operation mode
–
Read only
 
CiA: Active operation mode
-11
Identification
-10
Test mode
-3
MS: Position mode
-2
MS: Velocity mode
Vendor specific velocity mode
-1
MS: Torque mode
Manufacturer-specific torque mode
0
No selection
No selection
2
CiA: Velocity mode (vl)
CiA: Velocity mode