IP settings

IP basic settings
The basic IP settings are required to let the engineering software access the network nodes (PLC, inverter) directly via Ethernet.
The PC with the engineering software must be in the same network as the devices to be configured.
First, configure the PC so that this condition is fulfilled.
The required steps are described by the example of the operating system Microsoft® Windows® 7.
How to define the IP basic settings:
1.
Call the "Network and sharing center" under "Control panel".
 
2.
Select "Change adapter settings" (observe administrator rights!).
 
3.
Select the network to be configured (double-click), e. g.:
The network nodes (PLC, inverter) must be connected to the network.
 
The status dialog box of the network is opened.
 
4.
Click "Properties".
The properties dialog box of the network is opened.
 
5.
Select "Internet protocol version 4 (TCP/IPv4)" and click "Properties".
The properties dialog box of the "Internet protocol version 4 (TCP/IPv4)" is opened.
 
6.
Enter the IP address, the subnet mask and, if required, the gateway address under "Use the following addresses".
 
7.
Click "OK".
 
The IP basic settings are now completed.
 
Set IP address
The IP address is set in 0x23B1:001.
–
0x23B2:001 shows the active IP address.
 
–
A value changed during operation only becomes valid with a network restart.
 
 
Time-To-Live (TTL)
The TTL value (8-bit value) limits the number of routers a sent package passes on the way to its target.
–
0x23A1:006: Time-to-live value (TTL)
 
 
The parameters for the IP settings of the inverter are described below.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x23B1:001
Modbus -TCP/IP settings: IP address
0.0.0.0 ... [192.168.124.16] ... 255.255.255.255
Set IP address.
The default setting 276605120 corresponds to the IP address 192.168.124.16.
–
276605120 = 0x107CA8C0
à
 0xC0.0xA8.0x7C.0x10 = 192.168.124.16
 
0x23B1:002
Modbus -TCP/IP settings: Subnet
0.0.0.0 ... [255.255.255.0] ... 255.255.255.255
Set subnet mask.
The default setting 16777215 corresponds to the subnet mask 255.255.255.0.
–
16777215 = 0xFFFFFF
à
 0xFF.0xFF.0xFF.0x00 = 255.255.255.0
 
0x23B1:003
Modbus -TCP/IP settings: Gateway
0.0.0.0 ... [0.0.0.0] ... 255.255.255.255
Set gateway address.
Example
The setting 276344004 corresponds to the gateway address 196.172.120.16.
–
276344004 = 0x1078ACC4
à
 0xC4.0xAC.0x78.0x10 = 196.172.120.16
 
0x23B1:005
Modbus -TCP/IP settings: IP configuration
Set IP configuration.
0
Stored IP
The currently saved IP configuration is used.
1
BOOTP
The IP configuration is assigned by the client via BOOTP.
2
DHCP
The IP configuration is assigned by the client via DHCP.
The assignment of a gateway address that is not in the same subnetwork as the IP address, is denied.
0x23B1:006
Modbus -TCP/IP settings: Time-to-live value (TTL)
1 ... [32] ... 255
Setting of the TTL value for the validity of data packages in the network.
0x23B1:011
Modbus -TCP/IP settings: Secondary port
0 ... [502] ... 65535
Set port number for a second port.