FSoE connection

Fail-safe-over-EtherCAT (FSoE) enables the transmission of safe information via FSoE protocol according to ETG.5100 S specification, version 1.2.0 of the EtherCAT user organisation (ETG).
Safety over EtherCAT® is a registered trademark and patented technology, licensed by Beckhoff Automation GmbH, Germany.
 
Addressing
A definite FsoE address ensures that a data frame reaches the correct node. If "FSoE" has been selected as safety bus, the safety address is at the same time accepted as the FSoE target address. This address must match the corresponding configuration of the safety PLC.
 
The checksums (CRC) of a parameter set are calculated via the set safety parameters. The calculated checksums of the safety parameter set must match the corresponding configuration of the safety PLC.
 
 
Structure of the FSoE output data
The safety PLC sends FSoE output data (control commands) to the inverter:
–
Data length: 11 bytes
 
–
Control commands are LOW-active; a bit value of "0" activates the function.
 
–
Exceptions: See the information in the table.
 
Byte offset
Bit offset
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Byte 0
Command (CMD)
Byte 1
AIE
(0↗1)
-
-
-
-
-
SS1
STO
Byte 2
SSE
-
ES
(HIGH active)
-
OMS
(HIGH active)
-
-
AIS
(0↗1)
Byte 3
CRC_0 (Low-Byte)
Byte 4
CRC_0 (High-Byte)
Byte 5
-
-
-
-
-
-
-
-
Byte 6
-
-
-
-
-
-
SD-Out1
(HIGH active)
-
Byte 7
CRC_1 (Low-Byte)
Byte 8
CRC_1 (High-Byte)
Byte 9
Connection-ID (Low-Byte)
Byte 10
Connection-ID (High-Byte)
 
Structure of the FSoE input data
The inverter sends FSoE input data (status information) to the safety PLC:
–
Data length: 31 bytes
 
–
Status information is HIGH-active; a bit value of "1" indicates that the status information is active.
 
Byte offset
Bit offset
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Byte 0
Command (CMD)
Byte 1
Error active
-
-
-
-
-
-
STO active
Byte 2
SSE active
-
ES active
-
OMS active
-
-
SS1 active
Byte 3
CRC_0 (Low-Byte)
Byte 4
CRC_0 (High-Byte)
Byte 5
-
-
-
-
-
-
-
-
Byte 6
-
-
-
-
-
-
-
-
Byte 7
CRC_1 (Low-Byte)
Byte 8
CRC_1 (High-Byte)
Byte 9
-
-
-
-
-
-
-
-
Byte 10
-
-
-
-
MUT active
-
-
-
Byte 11
CRC_2 (Low-Byte)
Byte 12
CRC_2 (High-Byte)
Byte 13
SD-In2-B
SD-In2-A
SD-In1-B
SD-In1-A
-
-
SD-In2
SD-In1
Byte 14
SD-In-AIS
SD-In-AIE
-
-
-
-
-
SD-Out1
Byte 15
CRC_3 (Low-Byte)
Byte 16
CRC_3 (High-Byte)
Byte 17
-
Byte 18
-
Byte 19
CRC_4 (Low-Byte)
Byte 20
CRC_4 (High-Byte)
Byte 21
-
Byte 22
-
Byte 23
CRC_5 (Low-Byte)
Byte 24
CRC_5 (High-Byte)
Byte 25
-
Byte 26
-
Byte 27
CRC_6 (Low-Byte)
Byte 28
CRC_6 (High-Byte)
Byte 29
Connection-ID (Low-Byte)
Byte 30
Connection-ID (High-Byte)
 
Parameter
Address
Name / setting range / [default setting]
Information
0x212A:001
S-Bus: FSoE project CRC
0 ... [0] ... 4294967295
–
Safety parameter (Safety parameter list)
 
0xE600:001
FSoE Slave Frame Elements: Command
–
Read only
 
0xE600:002
FSoE Slave Frame Elements: Connection ID
–
Read only
 
0xE600:003
FSoE Slave Frame Elements: CRC_0
–
Read only
 
0xE600:004
FSoE Slave Frame Elements: CRC_1
–
Read only
 
0xE600:005
FSoE Slave Frame Elements: CRC_2
–
Read only
 
0xE600:006
FSoE Slave Frame Elements: CRC_3
–
Read only
 
0xE600:007
FSoE Slave Frame Elements: CRC_4
–
Read only
 
0xE700:001
FSoE Master Frame Elements: Command
–
Read only
 
0xE700:002
FSoE Master Frame Elements: Connection ID
–
Read only
 
0xE700:003
FSoE Master Frame Elements: CRC_0
–
Read only
 
0xE700:004
FSoE Master Frame Elements: CRC_1
–
Read only
 
0xE700:005
FSoE Master Frame Elements: CRC_2
–
Read only
 
0xE901:001
FSoE Connection Communication Parameter: Version
–
Read only
 
0xE901:002
FSoE Connection Communication Parameter: Safety address
–
Read only
 
Value range: 1 ... 65534
Default setting: 1
0xE901:003
FSoE Connection Communication Parameter: Connection ID
–
Read only
 
0xE901:004
FSoE Connection Communication Parameter: Watchdog Time
–
Read only
 
Value range: 30 ... 5000 ms
Default setting: 100 ms
0xE901:006
FSoE Connection Communication Parameter: Connection Type
–
Read only
 
0
Master Connection
1
Slave Connection
0xE901:007
FSoE Connection Communication Parameter: Communication Parameter Length
–
Read only
 
0xE901:008
FSoE Connection Communication Parameter: Application Parameter Length
–
Read only
 
0xEA00:001
S-Bus: FSoE status
–
Read only
 
0
Reset
1
Session
2
Connection
3
Parameter
4
Data
5
Failsafe