Expert settings

–
The sync managers are configured for the cyclic data transfer and the mailbox communication (display in 0x1C00:001 ... 0x1C00:004).
 
–
For the communication, the I/O data mapping must be configured via  ... 0x1C12:002 (for RPDOs) and  ... 0x1C13:002 (for TPDOs).
 
–
The basic settings for the sync managers are made via 0x1C32:001 ... 0x1C32:005 and 0x1C33:001 ... 0x1C33:005.
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x1C00:001
Sync manager type: SM0 communication type
–
Read only
 
The communication type SM1 is used for the mailbox input (MbxIn).
0x1C00:002
Sync manager type: SM1 communication type
–
Read only
 
The communication type SM2 is used for the mailbox output (MbxOut).
0x1C00:003
Sync manager type: SM2 communication type
–
Read only
 
The communication type SM3 is used for the input process data (RPDOs).
0x1C00:004
Sync manager type: SM3 communication type
–
Read only
 
The communication type SM4 is used for the output process data (TPDOs).
0x1C12:001
SM2 PDO assignment: PDO mapping object index of 1. assigned RPDO
–
Read only
 
Display of the mapping object index of RPDO1.
0x1C12:002
SM2 PDO assignment: PDO mapping object index of 2. assigned RPDO
–
Read only
 
Display of the mapping object index of RPDO2.
0x1C13:001
SM3 PDO assignment: PDO mapping object index of 1. assigned TPDO
–
Read only
 
Display of the mapping object index of TPDO1.
0x1C13:002
SM3 PDO assignment: PDO mapping object index of 2. assigned TPDO
–
Read only
 
Display of the mapping object index of TPDO2.
0x1C32:001
Sync Manager 2: Synchronization type
–
Read only
 
–
From version 02.00
 
Settings of the synchronisation method for the mailbox communication.
0x1C32:002
Sync Manager 2: Cycle time
–
Read only: x ns
 
–
From version 02.00
 
Display of the cycle time for the mailbox communication.
0x1C32:003
Sync Manager 2: Shift time
–
Read only: x ns
 
–
From version 02.00
 
Display of the time shift for the mailbox communication.
0x1C32:004
Sync Manager 2: Sync modes supported
–
Read only
 
–
From version 02.00
 
Display of the available synchronisation method for the mailbox communication.
–
Bit 0 (free run)
 
0x1C32:005
Sync Manager 2: Minimum cycle time
–
Read only: x ns
 
–
From version 02.00
 
Display of the minimum cycle time for the mailbox communication.
0x1C33:001
Sync Manager 3: Synchronization type
–
Read only
 
–
From version 02.00
 
Setting of the synchronisation method for the input process data (RPDO).
0x1C33:002
Sync Manager 3: Cycle time
–
Read only: x ns
 
–
From version 02.00
 
Display of the cycle time for the input process data (RPDO).
0x1C33:003
Sync Manager 3: Shift time
–
Read only: x ns
 
–
From version 02.00
 
Display of the time shift for the input process data (RPDO).
0x1C33:004
Sync Manager 3: Sync modes supported
–
Read only
 
–
From version 02.00
 
Display of the available synchronisation method for the input process data (RPDO).
–
Bit 0 (free run)
 
0x1C33:005
Sync Manager 3: Minimum cycle time
–
Read only: x ns
 
–
From version 02.00
 
Display of the minimum cycle time for the input process data (RPDO).