Station name and IP configuration
The station name and the IP configuration can be assigned by the IO-Controller. These settings enable the IO-Controllerto identify the devices in the network and manage the data exchange.
The station name and the IP configuration can also be assigned by the »Engineering Tool«.
–
The station name of the IO device must be entered with permissible characters according to the PROFINET specification.
0x2381:004 (P510.04)
0x2381:004 (P510.04)–
Display of the currently used station name:
0x2382:004 (P511.04)
0x2382:004 (P511.04)–
The IP configuration comprises the assignments of:
–
IP address
0x2381:001 (P510.01)
0x2381:001 (P510.01)–
Subnet mask
0x2381:002 (P510.02)
0x2381:002 (P510.02)–
Gateway address
0x2381:003 (P510.03)
0x2381:003 (P510.03)–
Display of the actual IP configuration:
0x2382:001 (P511.01) ... 0x2382:003 (P511.03)
0x2382:001 (P511.01) ... 0x2382:003 (P511.03)Save the station name and the IP configuration in the IO Device with line voltage failure protection so the IO Device can be identified via PROFINET if the IO controller is switched off. 0x2022:003 (P700.03)
An invalid station name or the assignment of invalid combinations of the IP address, subnet mask, and gateway address can have the consequence that no connection to PROFINET can be established.
In case of impermissible settings, the red LED "bus ERR" is blinking and the error message "PROFINET: Stack initialization error [0x8192]" is output.
Parameter
|
Address
|
Name / setting range / [default setting]
|
Information
|
|
|
0x2381:001
(P510.01)
|
PROFINET settings: IP address
(PROFINET sett.: IP address)
0.0.0.0 ... [0.0.0.0] ... 255.255.255.255
–
From version 02.00
|
Set IP address
–
A changed value will only be effective after the PROFINET communication is restarted (0x2380 (P508.00) = 1).
|
|
|
0x2381:002
(P510.02)
|
PROFINET settings: Subnet
(PROFINET sett.: Subnet)
0.0.0.0 ... [0.0.0.0] ... 255.255.255.255
–
From version 02.00
|
Set subnet mask
–
A changed value will only be effective after the PROFINET communication is restarted (0x2380 (P508.00) = 1).
|
|
|
0x2381:003
(P510.03)
|
PROFINET settings: Gateway
(PROFINET sett.: Gateway)
0.0.0.0 ... [0.0.0.0] ... 255.255.255.255
–
From version 02.00
|
Set gateway address
–
A changed value will only be effective after the PROFINET communication is restarted (0x2380 (P508.00) = 1).
–
The gateway address is valid if the network address of the IP address is identical to the gateway address. In this case, no gateway functionality is used.
–
DHCP is not supported.
|
|
|
0x2381:004
(P510.04)
|
PROFINET settings: Station name
(PROFINET sett.: Stationsname)
–
From version 02.00
|
Set station name
–
A changed value will only be effective after the PROFINET communication is restarted (0x2380 (P508.00) = 1).
|
|
|
0x2381:005
|
PROFINET settings: I&M1 System designation
–
From version 02.00
|
Input/output of the I&M1 system designation
–
The default setting is an empty string.
|
|
|
0x2381:006
|
PROFINET settings: I&M1 Installation site
–
From version 02.00
|
Input/output of the I&M1 location identification code
–
The default setting is an empty string.
|
|
|
0x2381:007
|
PROFINET settings: I&M2 Installation date
–
From version 02.00
|
Input/output of the I&M2 date of installation
–
The default setting is an empty string.
|
|
|
0x2381:008
|
PROFINET settings: I&M3 additional information
–
From version 02.00
|
Input/output of the I&M3 additional information
–
The default setting is an empty string.
|
|
|
0x2381:009
|
PROFINET settings: I&M4 signature code
–
From version 02.00
|
Input/output of the I&M4 signature
–
The default setting is an empty string.
|
|