Basic setting and options
Compared to an i550 inverter without IO-Link, an i550 inverter with IO-Link has some different default settings:
|
Parameter
|
Standard value
|
|
Network control: = TRUE
|
|
|
Constant TRUE [1]
|
|
|
Standard frequency setpoint source = Network [5]
|
|
|
PID control Standard setpoint source = Network = [5]
|
|
|
Torque control Standard setpoint source = [5]
|
|
|
NetWordIN2.15 [49]
|
|
|
NetWordIN2.14 [48]
|
|
|
NetWordIN3 [20]
|
Error responses or events
When an event occurs, the IO-Link device reports an "Event Flag" to the IO-Link master. The IO-Link master recognizes the "Event Flag" and reads the reported event. While an event is read, no parameter data can be exchanged, because the "on-request data" time block (Device reply message) is used for transmitting the event data. Three event categories are defined:
–
Error messages (error)
–
Maintenance data (warnings)
–
IO-Link device functions (notifications)
Recording error information
There are two options to record error information on IO-Link:
–
Via the IO-Link "event" mechanism
–
Via the "Read-out of the device history buffer" device function (SDO communication)
IO-Link “event” mechanism
Three different event categories (according to IO-Link specification) are transmitted to the PLC via the IO-Link master. Each "Event" IO-Link category has an "error response" of a particular IO-Link device.
|
IO-Link event
|
IO-Link device (error response)
|
|
Error messages (error)
|
Errors and problems
|
|
Maintenance data (warnings)
|
Warning
|
|
IO-Link device functions (notifications)
|
No response
|
Example:
|
#
|
Title
|
IO-Link device
“Error code”
|
IO-Link "error code"
|
IO-Link device
(Error response)
|
IO-Link event
|
|
1
|
No memory module
|
0c7681
|
0x1843
|
Error
|
Error messages
(Error)
|
|
2
|
Cooling fan warning
|
0x4281
|
0x1813
|
Warning
|
Maintenance data
(Warnings)
|
|
3
|
Max. current reached
|
0x238A
|
0x1809
|
No response
|
IO-Link device functions
(Notifications)
|
IO-Link error codes
Error messages that are transmitted to the PLC via the IO-Link master do not have the same error coding as the IO-Link device. In accordance with the IO-Link specification, the following manufacturer-specific "error codes" are given:
–
0x1800 to 0x18FF
In order to obtain a clear identification for each IO-Link error, a unique IO-Link "error code" is assigned to each of them.
See the example in previous table or IO-Link event IDs.
Reading out the device protocol buffer (SDO communication)
This mechanism allows you to access and read out all logbook data. In order to address the respective parameter, the SDO channel must be used.
Read out error history buffer