IO-Link event IDs
The IO-Link error codes differ from the Lenze error codes. According to the IO-Link specification, manufacturer-specific "error codes" are listed in the following table.
–
Clicking the details of the error code shows you a detailed description of the error message.
–
If the inverter indicates an "internal error" that is not listed here, restart the inverter. If the error persists, make a note of the error code and contact the manufacturer.
|
Event ID
|
Event
|
Severity
|
Details
|
|
0x1801
|
CiA: Continuous over current (internal)
|
Fault
|
|
|
0x1802
|
Short circuit or earth leakage at the motor end
|
Fault
|
|
|
0x1803
|
Short circuit at the motor end
|
Fault
|
|
|
0x1804
|
CiA: i²xt overload (thermal state)
|
Fault
|
|
|
0x1805
|
Fault - Device utilization (ixt) too high
|
Fault
|
|
|
0x1806
|
Warning - Device utilization (ixt) too high
|
Warning
|
|
|
0x1807
|
Clamp responded too often
|
Fault
|
|
|
0x1808
|
Sensorless control: stall detection active
|
Trouble
|
|
|
0x1809
|
Maximum current reached
|
Information
|
|
|
0x180A
|
Mains phase fault
|
Fault
|
|
|
0x180B
|
UPS operation active
|
Warning
|
|
|
0x180C
|
Fault - DC bus overvoltage
|
Fault
|
|
|
0x180D
|
DC bus overvoltage warning
|
Warning
|
|
|
0x180E
|
Fault - DC bus undervoltage
|
Trouble
|
|
|
0x180F
|
DC bus undervoltage warning
|
Warning
|
|
|
0x1810
|
DC-bus voltage too low for power up
|
Warning
|
|
|
0x1811
|
Fault - Power unit overtemperature
|
Fault
|
|
|
0x1812
|
Fault - Heat sink temperature sensor
|
Fault
|
|
|
0x1813
|
Heat sink fan warning
|
Warning
|
|
|
0x1814
|
PU overtemperature warning
|
Warning
|
|
|
0x1815
|
Motor overtemperature
|
Fault
|
|
|
0x1816
|
External supply voltage critical
|
Warning
|
|
|
0x1817
|
Overload 24 V supply
|
Warning
|
|
|
0x1818
|
OEM hardware incompatible
|
Fault
|
|
|
0x1820
|
Warning - Internal fan
|
Warning
|
|
|
0x182A
|
Trigger/functions connected incorrectly
|
Trouble
|
|
|
0x182B
|
User-defined fault 1
|
Fault
|
|
|
0x182C
|
User-defined fault 2
|
Fault
|
|
|
0x182D
|
Warning invert rotation
|
Warning
|
|
|
0x182E
|
Maximuml allowed troubles exceeded
|
Fault
|
|
|
0x182F
|
User-defined fault (LECOM)
|
Fault
|
|
|
0x1830
|
Network: user fault 1
|
Fault
|
|
|
0x1831
|
Network: user fault 2
|
Fault
|
|
|
0x1832
|
NetWordIN1 configuration incorrect
|
Trouble
|
|
|
0x1890
|
Changed device ID not yet active
|
Fault
|
|
|
0x1891
|
Default settings not yet active
|
Fault
|
|
|
0x1834
|
CU: load error ID tag
|
Fault
|
|
|
0x1835
|
PU: load error ID tag
|
Fault
|
|
|
0x1836
|
Power unit unknown
|
Fault
|
|
|
0x1838
|
Assertion level monitoring (Low/High)
|
Fault
|
|
|
0x1839
|
Analog input 1 fault
|
Fault
|
|
|
0x183A
|
Analog input 2 fault
|
Fault
|
|
|
0x183B
|
HTL input fault
|
No response
|
|
|
0x183C
|
Analog output 1 fault
|
Warning
|
|
|
0x183D
|
Analog output 2 fault
|
Warning
|
|
|
0x183E
|
Fault - Pole position identification
|
Fault
|
|
|
0x183F
|
Motor overcurrent
|
Fault
|
|
|
0x1840
|
Encoder open circuit
|
Warning
|
|
|
0x1841
|
Feedback system: speed limit
|
Warning
|
|
|
0x1842
|
Memory module is full
|
Warning
|
|
|
0x1843
|
Memory module not present
|
Fault
|
|
|
0x1844
|
Invalid user data
|
Fault
|
|
|
0x1845
|
Data not compl. saved before powerdown
|
Warning
|
|
|
0x1848
|
Memory module: invalid OEM data
|
Warning
|
|
|
0x1849
|
Memory module: wrong type
|
Fault
|
|
|
0x184A
|
EPM firmware version incompatible
|
Fault
|
|
|
0x184B
|
EPM data: firmware type incompatible
|
Fault
|
|
|
0x184C
|
EPM data: new firmware type detected
|
Fault
|
|
|
0x184D
|
EPM data: PU size incompatible
|
Fault
|
|
|
0x184E
|
EPM data: new PU size detected
|
Fault
|
|
|
0x184F
|
Invalid parameter changeover configuration
|
Warning
|
|
|
0x1850
|
EPM data: unknown parameter found
|
Information
|
|
|
0x1851
|
Parameter changes lost
|
Fault
|
|
|
0x1852
|
Network - Time-out explicit message
|
Warning
|
|
|
0x1853
|
Network - Overall communication time-out
|
Warning
|
|
|
0x1854
|
Time-out (PAM)
|
No response
|
|
|
0x1855
|
Modbus TCP master time-out
|
Fault
|
|
|
0x1856
|
Modbus TCP Keep Alive time-out
|
Fault
|
|
|
0x1858
|
CAN: bus off
|
Trouble
|
|
|
0x1859
|
CAN: warning
|
Warning
|
|
|
0x185A
|
CAN: heartbeat time-out consumer 1
|
Fault
|
|
|
0x185B
|
CAN: heartbeat time-out consumer 2
|
Fault
|
|
|
0x185C
|
CAN: heartbeat time-out consumer 3
|
Fault
|
|
|
0x185D
|
CAN: heartbeat time-out consumer 4
|
Fault
|
|
|
0x185E
|
Network - Watchdog time-out
|
Trouble
|
|
|
0x185F
|
Network - Disruption of cyclic data exchange
|
No response
|
|
|
0x1860
|
Network - Initialization error
|
Trouble
|
|
|
0x1861
|
Network - Invalid cyclic process data
|
Trouble
|
|
|
0x1863
|
Modbus: network time-out
|
Fault
|
|
|
0x1864
|
Modbus: incorrect request by master
|
Warning
|
|
|
0x1865
|
Network communication faulty
|
Trouble
|
|
|
0x1866
|
POWERLINK: Loss of SoC
|
Trouble
|
|
|
0x1867
|
POWERLINK: CRC error
|
Trouble
|
|
|
0x1868
|
Network - PDO mapping error
|
Trouble
|
|
|
0x1869
|
CAN: RPDO1 time-out
|
Fault
|
|
|
0x186A
|
CAN: RPDO2 time-out
|
Fault
|
|
|
0x186B
|
CAN: RPDO3 time-out
|
Fault
|
|
|
0x186C
|
Torque limit reached
|
No response
|
|
|
0x186D
|
Function not allowed in selected operating mode
|
Warning
|
|
|
0x186E
|
Keypad removed
|
Fault
|
|
|
0x186F
|
Fault - Brake resistor overload
|
Fault
|
|
|
0x1870
|
Safe torque off (STO) activated
|
Fault
|
|
|
0x1871
|
Motor overspeed
|
Fault
|
|
|
0x1872
|
Motor phase missing
|
No response
|
|
|
0x1873
|
Motor phase failure phase U
|
No response
|
|
|
0x1874
|
Motor phase failure phase V
|
No response
|
|
|
0x1875
|
Motor phase failure phase W
|
No response
|
|
|
0x1876
|
Motor parameter identification fault
|
Fault
|
|
|
0x1877
|
FMF Error
|
Fault
|
|
|
0x188F
|
Cascading overload
|
Warning
|
|
|
0x187E
|
Warning - Brake resistor overload
|
Warning
|
|
|
0x187F
|
Automatic start disabled
|
Fault
|
|
|
0x1880
|
Load loss detected
|
No response
|
|
|
0x1881
|
Motor overload
|
No response
|
|
|
0x1882
|
Maximum motor frequency reached
|
Warning
|
|
|
0x188c
|
Manual mode disabled
|
Warning
|
|
|
0x188d
|
Manual mode activated
|
Warning
|
|
|
0x188e
|
Manual mode time-out
|
Fault
|
|
|
|
Safety option - Internal error
|
Fault
|
|
|
0x1883
|
Wrong password
|
Warning
|
|
|
0x1884
|
Warning
|
Warning
|
|
|
0x1885
|
Fatal Error
|
Fault
|
|
|
0x1886
|
Power unit fatal error
|
Fault
|
|
|
0x1888
|
Keypad full control active
|
Warning
|
8784