Data mapping

Data mapping defines which process data is exchanged cyclically between IO-Link master and IO-Link device. The PDO mapping process cannot be applied to all parameters.
The mapping objects are saved in the IO-Link device:
–
Internal mapping of the process input data: 0x24E0:001 ... 0x24E0:012
 
–
Internal mapping of the process output data: 0x24E1:001 ... 0x24E1:012
 
Definition of the process input data
#
Description
R/W
Index
1
RPDO mapping entry 1
R/W
2
RPDO mapping entry 2
R/W
3
RPDO mapping entry 3
R/W
4
RPDO mapping entry 4
R/W
5
RPDO mapping entry 5
R/W
6
RPDO mapping entry 6
R/W
7
RPDO mapping entry 7
R/W
8
RPDO mapping entry 8
R/W
9
RPDO mapping entry 9
R/W
10
RPDO mapping entry 10
R/W
11
RPDO mapping entry 11
R/W
12
RPDO mapping entry 12
R/W
Definition of the process output data
#
Description
R/W
Index
1
TPDO mapping entry 1
R/W
2
TPDO mapping entry 2
R/W
3
TPDO mapping entry 3
R/W
4
TPDO mapping entry 4
R/W
5
TPDO mapping entry 5
R/W
6
TPDO mapping entry 6
R/W
7
TPDO mapping entry 7
R/W
8
TPDO mapping entry 8
R/W
9
TPDO mapping entry 9
R/W
10
TPDO mapping entry 10
R/W
11
TPDO mapping entry 11
R/W
12
TPDO mapping entry 12
R/W
 
Data mapping via controller or Engineering Tool (EASY Starter)
 
Dynamic PDO mapping (receive and transmit data) can be carried out in two ways:
–
Via the Lenze user interface → EASY Starter
 
–
Via the acyclic data transmission.
 
 
How to configure dynamic PDO mapping parameters via the SDO channel:
Deactivate PDO communication
1.
Deactivate RPDO:
 
a.
Via controller or Lenze Engineering Tool: 0x24E0:000 = 0
 
b.
Via IO-Link master tool : 0x24E0:020 = 0
 
2.
Deactivate TPDO:
 
a.
Via controller or Lenze Engineering Tool: 0x24E1:000 = 0
 
b.
Via IO-Link master tool : 0x24E1:020 = 0
 
 
Define mapping.
1.
Assign parameters to the RPDOs in 0x24E0 in the format "0xiiiissll".
(iiii= Index hexadecimal, ss= subindex hexadecimal, ll= data length hexadecimal)
 
2.
Assign parameters to the TPDOs in 0x24E1 in the format "0xiiiissll".
(iiii= Index hexadecimal, ss= subindex hexadecimal, ll= data length hexadecimal)
Example:
Assign index 0x4008:001 with data length 16 bit to RPDO 1:
iiii = 4008, ss = 01, II = 10 → 0x24E0:001 = 0x40080110
 
 
Reactivate PDO communication.
1.
Activate RPDO:
 
a.
Via controller or Lenze Engineering Tool: 0x24E0:000 = Number of mapped parameters
 
b.
Via IO-Link master tool : 0x24E0:020 = Number of mapped parameters
 
2.
Activate TPDO:
 
a.
Via controller or Lenze Engineering Tool: 0x24E1:000 = Number of mapped parameters
 
b.
Via IO-Link master tool : 0x24E1:020 = Number of mapped parameters
 
 
The mapping value must cover the device index, not the IO-Link index. Only parameters that are marked as "mappable" with the attribute "r,t" or "rt" can be mapped. Parameter attribute list
 
 
Standard RPDO mapping
The assignment of different bits with the same function is not permissible.
 
For the process data from IO-Link master to the inverter, the following data mapping is preset in the IO-Link device description file (IODD):
IO-Link master --> IO-Link device
0x231D = [3]: 6 Byte PDO
0x231D = [1]: 12 Byte PDO
RPDO mapping entry 1
NetWordIN1 data word 0x4008:001 (P590.01)
NetWordIN1 data word 0x4008:001 (P590.01)
RPDO mapping entry 2
Setpoint frequency 0x400B:005 (P592.05)
NetWordIN2 data word 0x4008:002 (P590.02)
RPDO mapping entry 3
NetWordIN2 data word 0x4008:002 (P590.02)
NetWordIN3 data word 0x4008:003 (P590.03)
RPDO mapping entry 4
-
Setpoint frequency 0x400B:005 (P592.05)
RPDO mapping entry 5
-
PID setpoints 0x400B:007 (P592.07)
RPDO mapping entry 6
-
Torque setpoint 0x400B:008 (P592.08)
Function assignment of the NetWordIN1 data word
 
Standard TPDO mapping
The assignment of different bits with the same function is not permissible.
 
For the process data from IO-Link master to the inverter, the following data mapping is preset in the IO-Link device description file (IODD):
IO-Link device --> IO-Link master
0x231D = [3]: 6 Byte PDO
0x231D = [1]: 12 Byte PDO
TPDO mapping entry 1
TPDO mapping entry 2
Digital input status 0x60FD (P118.00)
Device actual utilisation 0x2D40:004 (P135.04)
TPDO mapping entry 3
-
Motor current 0x2D88 (P104.00)
TPDO mapping entry 4
-
Output frequency 0x2DDD (P100.00)
TPDO mapping entry 5
-
Current process variable 0x401F:002 (P121.02)
TPDO mapping entry 6
-
Actual torque 0x6077 (P107.00)
Function assignment of the NetWordOUT1 data word: