Output data/assemblies are created by the PLC (Scanner) and transmitted to the inverter (Adapter).
–
Input data/assemblies are created by the inverter (Adapter) and transmitted to the PLC (Scanner).
|
|
Process data transfer (Implicit Messaging)
Parameter data transfer (Explicit Messaging)|
Attribute ID
|
Name
|
Info / parameter
|
|
Assembly output object instances according to AC-Drive profile
|
||
|
20
|
Basic Speed Control Output
|
Bit 0 and 2 of the LSB of the AC drive control word 0x400B:001 (P592.01)
0x400B:004 (P592.04) Network setpoint speed |
|
21
|
Extended Speed Control Output
|
LSB of the AC drive control word 0x400B:001 (P592.01)
0x400B:004 (P592.04) Network setpoint speed |
|
22
|
Speed and Torque Control Output
|
Bit 0 and 2 of the LSB of the AC drive control word 0x400B:001 (P592.01)
0x400B:004 (P592.04) Network setpoint speed 0x400B:008 (P592.08) Torque mode setpoint |
|
23
|
Extended Speed and Torque Control Output
|
LSB of the AC drive control word 0x400B:001 (P592.01)
0x400B:004 (P592.04) Network setpoint speed 0x400B:008 (P592.08) Torque mode setpoint |
|
Assembly input object instances according to AC drive profile
|
||
|
70
|
Basic Speed Control Input
|
Bit 0 and 2 of the LSB of the AC drive status word 0x400C:001 (P593.01)
0x400C:004 (P593.04) Motor speed |
|
71
|
Extended Speed Control Input
|
LSB from AC drive status word 0x400C:001 (P593.01)
MSB Drive State of the AC drive status word (mask bits 12 ... 15)
0x400C:004 (P593.04) Motor speed |
|
72
|
Speed and Torque Control Input
|
Bit 0 and 2 of the LSB of the AC drive status word 0x400C:001 (P593.01)
0x400C:004 (P593.04) Motor speed 0x400C:007 (P593.07) Torque scaled |
|
73
|
Extended Speed and Torque Control Input
|
LSB from AC drive status word 0x400C:001 (P593.01)
MSB Drive State of the AC drive status word (mask bits 12 ... 15)
0x400C:004 (P593.04) Motor speed 0x400C:007 (P593.07) Torque scaled |
|
Assembly object instances for customer-specific configurations
|
||
|
110
|
Custom Output
|
Control data sent to the inverter
Data size: mapped data + 4 byte header
–
Depending on your controller, you may need to add the 4-byte header manually.
|
|
111
|
Custom Input
|
Status data sent by the inverter
Data size: mapped data + 4 byte header
–
Depending on your controller, you may need to add the 4-byte header manually.
|
|
130
|
Configuration
|
Data for configuring the assembly object instances 110 and 111
Data size:
–
68 bytes when used with 110 and 111
–
0 bytes for all other assembly object instances
|
|
Assembly object instances according to CIP Safety profile (only for inverters with "Extended Safety")
|
||
|
161
|
Safety Output with STO
|
CIP Safety output data
|
|
171
|
Safety Input with STO
|
CIP Safety input data
|
|
Attribute ID
|
Service
|
Name
|
Data type
|
Value
|
|
3
|
Get/Set
|
Data
|
Array of octet
|
Instance/class-specific
|
|
4
|
Get
|
Size
|
UINT
|
Number of bytes in attribute 3 (Data), instance/class-specific
|
|
Service code
|
Name
|
Information
|
|
0x0E
|
Get_Attribute_Single
|
Outputs the value of a specific attribute.
|
|
0x10
|
Set_Attribute_Single
|
Changes the value of a specific attribute.
|
|
Name
|
Value
|
Size [byte]
|
|
Input 1
|
Input parameter
|
2
|
|
Input 2
|
Input parameter
|
2
|
|
Input 3
|
Input parameter
|
2
|
|
Input 4
|
Input parameter
|
2
|
|
Input 5
|
Input parameter
|
2
|
|
Input 6
|
Input parameter
|
2
|
|
Input 7
|
Input parameter
|
2
|
|
Input 8
|
Input parameter
|
2
|
|
Input 9
|
Input parameter
|
2
|
|
Input 10
|
Input parameter
|
2
|
|
Input 11
|
Input parameter
|
2
|
|
Input 12
|
Input parameter
|
2
|
|
Input 13
|
Input parameter
|
2
|
|
Input 14
|
Input parameter
|
2
|
|
Input 15
|
Input parameter
|
2
|
|
Input 16
|
Input parameter
|
2
|
|
Input Trailing Data
|
100
|
2
|
|
Output 1
|
Output parameter
|
2
|
|
Output 2
|
Output parameter
|
2
|
|
Output 3
|
Output parameter
|
2
|
|
Output 4
|
Output parameter
|
2
|
|
Output 5
|
Output parameter
|
2
|
|
Output 6
|
Output parameter
|
2
|
|
Output 7
|
Output parameter
|
2
|
|
Output 8
|
Output parameter
|
2
|
|
Output 9
|
Output parameter
|
2
|
|
Output 10
|
Output parameter
|
2
|
|
Output 11
|
Output parameter
|
2
|
|
Output 12
|
Output parameter
|
2
|
|
Output 13
|
Output parameter
|
2
|
|
Output 14
|
Output parameter
|
2
|
|
Output 15
|
Output parameter
|
2
|
|
Output 16
|
Output parameter
|
2
|
|
Output Trailing Data
|
101
|
2
|
|
Selection for "Input parameter"
|
|
Selection for "Output parameter"
|
||||
|
Value
|
Name
|
Size [byte]
|
Value
|
Name
|
Size [byte]
|
|
|
0
|
ignore
|
N/A
|
|
0
|
ignore
|
N/A
|
|
1
|
Generic SINT Input *
|
1
|
|
51
|
Generic SINT Output *
|
1
|
|
2
|
Generic INT Input *
|
2
|
|
52
|
Generic INT Output *
|
2
|
|
3
|
Generic DINT Input *
|
4
|
|
53
|
Generic DINT Output *
|
4
|
|
4
|
2B0B/0 Freq Setpoint Hz
|
2
|
|
54
|
2946/1 Trq Mode Hi Spd
|
4
|
|
5
|
2D40/4 Device Load Act.
|
2
|
|
55
|
2946/2 Trq Mode Lo Spd
|
4
|
|
6
|
2D4F/0 Motor i2t utiliz.
|
2
|
|
56
|
4008/1 NetWordIN1
|
2
|
|
7
|
2D82/0 Motor voltage
|
4
|
|
57
|
4008/2 NetWordIN2
|
2
|
|
8
|
2D88/0 Motor current
|
2
|
|
58
|
4008/3 NetWordIN3
|
2
|
|
9
|
2DA2/1 Effective Power
|
4
|
|
59
|
4008/4 NetWordIN4
|
2
|
|
10
|
2DA2/2 Apparent Power
|
4
|
|
60
|
400B/1 AC Drv Ctrl Word
|
2
|
|
11
|
2DA3/1 Energy Out Motor
|
4
|
|
61
|
400B/2 C0135 Ctrl Word
|
2
|
|
12
|
2DA3/2 Energy Out Gen.
|
4
|
|
62
|
400B/3 Net Spd Stpnt Hz
|
2
|
|
13
|
2DA4/1 Anlg In1 %
|
2
|
|
63
|
400B/4 Net Spd Stpnt RPM
|
2
|
|
14
|
2DA4/2 Anlg In1 Freq
|
2
|
|
64
|
400B/5 Net Spd 0.01 Hz
|
2
|
|
15
|
2DA4/3 Anlg In1 PidVal
|
2
|
|
65
|
400B/6 NetSpdSign 0.1Hz
|
2
|
|
16
|
2DA4/4 Anlg In1 TorqVal
|
2
|
|
66
|
400B/7 Net PID Stpnt
|
2
|
|
17
|
2DA5/1 Anlg In2 %
|
2
|
|
67
|
400B/8 Net Torque Stpnt
|
2
|
|
18
|
2DA5/2 Anlg In2 Freq
|
2
|
|
68
|
6040/0 Control Word
|
2
|
|
19
|
2DA5/3 Anlg In2 PidVal
|
2
|
|
69
|
6042/0 Target Velocity
|
2
|
|
20
|
2DA5/4 Anlg In2 TorqVal
|
2
|
|
70
|
6046/1 Velocity Min
|
4
|
|
21
|
2DAA/1 AO1 Value (VDC)
|
2
|
|
71
|
6046/2 Velocity Max
|
4
|
|
22
|
2DAA/2 AO1 Value (IDC)
|
2
|
|
72
|
6048/1 Delta Speed
|
4
|
|
24
|
2DD3/1 Speed set
|
4
|
|
73
|
6048/2 Delta Time
|
2
|
|
26
|
2DDD/0 Actual Frequency
|
2
|
|
74
|
6049/1 Delta Speed
|
4
|
|
27
|
400A/1 NetWordOUT1
|
2
|
|
75
|
6049/2 Delta Time
|
2
|
|
28
|
400A/2 NetWordOUT2
|
2
|
|
76
|
6060/0 402 Control Modes
|
1
|
|
29
|
400C/1 AC Drv Stat Word
|
2
|
|
77
|
6071/0 402 Target Torque
|
2
|
|
30
|
400C/2 C0150 Stat Word
|
2
|
|
78
|
6080/0 Motor Max Speed
|
4
|
|
31
|
400C/3 Actual Speed Hz
|
2
|
|
79
|
60E0/0 Pos Torque Limit
|
2
|
|
32
|
400C/4 Actual Speed RPM
|
2
|
|
80
|
60E1/0 Neg Torque Limit
|
2
|
|
33
|
400C/5 Drive State
|
2
|
|
82
|
400B/13 Process Input Freq.
|
2
|
|
34
|
400C/6 Act Speed 0.01Hz
|
2
|
|
|
|
|
|
35
|
400C/7 Actual Torque Scaled
|
2
|
|
* Selection can be used to specify only the data size of the parameters in the PLC (Scanner). The desired parameters with the corresponding data size can then be assigned manually for the inverter (Adapter) in the »EASY Starter«:
"Settings" tab à Overview à Fieldbus EtherNet/IP à Mapping fieldbus dataData format of the parameters:
Parameter attribute list |
||
|
36
|
400D/0 Scaled Speed
|
2
|
|
|||
|
37
|
401F/1 Actual PID Stpnt
|
2
|
|
|||
|
38
|
401F/2 Actual PID Fbk
|
2
|
|
|||
|
39
|
401F/3 PID bits
|
1
|
|
|||
|
40
|
603F/0 Current Fault
|
2
|
|
|||
|
41
|
6041/0 Status Word
|
2
|
|
|||
|
42
|
6043/0 Velocity Demand
|
2
|
|
|||
|
43
|
6044/0 Velocity Actual
|
2
|
|
|||
|
44
|
6061/0 402 Mode Display
|
1
|
|
|||
|
45
|
6077/0 402 ActualTorq %
|
2
|
|
|||
|
46
|
6078/0 402 ActualCur %
|
2
|
|
|||
|
47
|
6079/0 402 DClink Volt
|
4
|
|
|||
|
48
|
60FD/0 Dig Inputs Stat
|
4
|
|
|||
|
50
|
400C/9 Process Output Freq.
|
2
|
|
|||
|
Attribute
(Instance ID)
|
Byte
|
Bit 7
|
Bit 6
|
Bit 5
|
Bit 4
|
Bit 3
|
Bit 2
|
Bit 1
|
Bit 0
|
|
20
(0x14)
|
0
|
|
|
|
|
|
FaultRst
|
|
RunFwd (CW)
|
|
1
|
|
||||||||
|
2
|
Speed Reference (low byte)
|
||||||||
|
3
|
Speed Reference (high byte)
|
||||||||
|
21
(0x15)
|
0
|
|
NetRef
|
NetCtrl
|
|
|
FaultRst
|
RunRev (CCW)
|
RunFwd (CW)
|
|
1
|
|
||||||||
|
2
|
Speed Reference (low byte)
|
||||||||
|
3
|
Speed Reference (high byte)
|
||||||||
|
22
(0x16)
|
0
|
|
|
|
|
|
FaultRst
|
|
RunFwd (CW)
|
|
1
|
|
||||||||
|
2
|
Speed Reference (low byte)
|
||||||||
|
3
|
Speed Reference (high byte)
|
||||||||
|
4
|
Torque Reference (low byte)
|
||||||||
|
5
|
Torque Reference (high byte)
|
||||||||
|
23
(0x17)
|
0
|
|
NetRef
|
NetCtrl
|
|
|
FaultRst
|
RunRev (CCW)
|
RunFwd (CW)
|
|
1
|
|
||||||||
|
2
|
Speed Reference (low byte)
|
||||||||
|
3
|
Speed Reference (high byte)
|
||||||||
|
4
|
Torque Reference (low byte)
|
||||||||
|
5
|
Torque Reference (high byte)
|
||||||||
|
110
(0x6E)
|
0
...
31
|
Custom Output
|
|||||||
|
Attribute
(Instance ID)
|
Byte
|
Bit 7
|
Bit 6
|
Bit 5
|
Bit 4
|
Bit 3
|
Bit 2
|
Bit 1
|
Bit 0
|
|
70
(0x46)
|
0
|
|
|
|
|
|
Running1
(Fwd, CW)
|
|
Faulted
|
|
1
|
|
||||||||
|
2
|
Speed Actual (low byte)
|
||||||||
|
3
|
Speed Actual (high byte)
|
||||||||
|
71
(0x47)
|
0
|
AtReference
|
RefFromNet
|
CtrlFromNet
|
Ready
|
Running2
(Rev, CCW)
|
Running1
(Fwd, CW)
|
Warning
|
Faulted
|
|
1
|
Drive State
|
||||||||
|
2
|
Speed Actual (low byte)
|
||||||||
|
3
|
Speed Actual (high byte)
|
||||||||
|
72
(0x48)
|
0
|
|
|
|
|
|
Running1
(Fwd, CW)
|
|
Faulted
|
|
1
|
|
||||||||
|
2
|
Speed Actual (low byte)
|
||||||||
|
3
|
Speed Actual (high byte)
|
||||||||
|
4
|
Torque Actual (low byte)
|
||||||||
|
5
|
Torque Actual (high byte)
|
||||||||
|
73
(0x49)
|
0
|
AtReference
|
RefFromNet
|
CtrlFromNet
|
Ready
|
Running2
(Rev, CCW)
|
Running1
(Fwd, CW)
|
Warning
|
Faulted
|
|
1
|
Drive State
|
||||||||
|
2
|
Speed Actual (low byte)
|
||||||||
|
3
|
Speed Actual (high byte)
|
||||||||
|
4
|
Torque Actual (low byte)
|
||||||||
|
5
|
Torque Actual (high byte)
|
||||||||
|
111
(0x6F)
|
0
...
31
|
Custom Input
|
|||||||