0x04-Assembly Object

The inverter contains EtherNet/IP assembly object instances which refer to the following »Studio 5000 Logix Designer®« connection parameters:
–
Inputs (actual value such as actual speed, actual position, etc.)
 
–
Outputs (enable and reference value for the drive)
 
–
Configuration
 
The inputs and outputs refer to the view of the PLC (Scanner).
–
Output data/assemblies are created by the PLC (Scanner) and transmitted to the inverter (Adapter).
 
–
Input data/assemblies are created by the inverter (Adapter) and transmitted to the PLC (Scanner).
 
 
The assembly object instances can be accessed via "Class 1 Messaging" (Implicit Messaging) and "Class 3 Messaging" (Explicit Messaging).
Customer specific configurations with the assembly object instances 110 and 111 are only possible with PLCs (Scanner) that support "Class 1 Messaging".
 
See also the following chapters:
Process data transfer  (Implicit Messaging)
Parameter data transfer  (Explicit Messaging)
 
The following predefined assembly object instances can be used in accordance with the "CIP™ Network Library":
Attribute ID
Name
Info / parameter
Assembly output object instances according to AC-Drive profile
20
Basic Speed Control Output
Bit 0 and 2 of the LSB of the AC drive control word 0x400B:001 (P592.01)
0x400B:004 (P592.04) Network setpoint speed
21
Extended Speed Control Output
LSB of the AC drive control word 0x400B:001 (P592.01)
0x400B:004 (P592.04) Network setpoint speed
22
Speed and Torque Control Output
Bit 0 and 2 of the LSB of the AC drive control word 0x400B:001 (P592.01)
0x400B:004 (P592.04) Network setpoint speed
0x400B:008 (P592.08) Torque mode setpoint
23
Extended Speed and Torque Control Output
LSB of the AC drive control word 0x400B:001 (P592.01)
0x400B:004 (P592.04) Network setpoint speed
0x400B:008 (P592.08) Torque mode setpoint
Assembly input object instances according to AC drive profile
70
Basic Speed Control Input
Bit 0 and 2 of the LSB of the AC drive status word 0x400C:001 (P593.01)
71
Extended Speed Control Input
LSB from AC drive status word 0x400C:001 (P593.01)
MSB Drive State of the AC drive status word (mask bits 12 ... 15)
72
Speed and Torque Control Input
Bit 0 and 2 of the LSB of the AC drive status word 0x400C:001 (P593.01)
0x400C:007 (P593.07) Torque scaled
73
Extended Speed and Torque Control Input
LSB from AC drive status word 0x400C:001 (P593.01)
MSB Drive State of the AC drive status word (mask bits 12 ... 15)
0x400C:007 (P593.07) Torque scaled
Assembly object instances for customer-specific configurations
110
Custom Output
Control data sent to the inverter
Data size: mapped data + 4 byte header
–
Depending on your controller, you may need to add the 4-byte header manually.
 
111
Custom Input
Status data sent by the inverter
Data size: mapped data + 4 byte header
–
Depending on your controller, you may need to add the 4-byte header manually.
 
130
Configuration
Data for configuring the assembly object instances 110 and 111
Data size:
–
68 bytes when used with 110 and 111
 
–
0 bytes for all other assembly object instances
 
Assembly object instances according to CIP Safety profile (only for inverters with "Extended Safety")
161
Safety Output with STO
CIP Safety output data
171
Safety Input with STO
CIP Safety input data
Instance attributes
Attribute ID
Service
Name
Data type
Value
3
Get/Set
Data
Array of octet
Instance/class-specific
4
Get
Size
UINT
Number of bytes in attribute 3 (Data), instance/class-specific
 
Supported service codes
Service code
Name
Information
0x0E
Get_Attribute_Single
Outputs the value of a specific attribute.
0x10
Set_Attribute_Single
Changes the value of a specific attribute.
 
Configuration Assembly 130 (68 bytes)
The configuration assembly is used to define the custom input and output objects (in conjunction with assemblies 110 and 111).
For any other assemblies, the data structure is predefined, therefore the configuration assembly is used with a data length of 0 bytes.
Structure of the Configuration Assembly 130
Name
Value
Size [byte]
Input 1
Input parameter
2
Input 2
Input parameter
2
Input 3
Input parameter
2
Input 4
Input parameter
2
Input 5
Input parameter
2
Input 6
Input parameter
2
Input 7
Input parameter
2
Input 8
Input parameter
2
Input 9
Input parameter
2
Input 10
Input parameter
2
Input 11
Input parameter
2
Input 12
Input parameter
2
Input 13
Input parameter
2
Input 14
Input parameter
2
Input 15
Input parameter
2
Input 16
Input parameter
2
Input Trailing Data
100
2
Output 1
Output parameter
2
Output 2
Output parameter
2
Output 3
Output parameter
2
Output 4
Output parameter
2
Output 5
Output parameter
2
Output 6
Output parameter
2
Output 7
Output parameter
2
Output 8
Output parameter
2
Output 9
Output parameter
2
Output 10
Output parameter
2
Output 11
Output parameter
2
Output 12
Output parameter
2
Output 13
Output parameter
2
Output 14
Output parameter
2
Output 15
Output parameter
2
Output 16
Output parameter
2
Output Trailing Data
101
2
Selection for “Input parameter” and “Output parameter” of the Configuration Assembly 130
Selection for "Input parameter"
Selection for "Output parameter"
Value
Name
Size [byte]
Value
Name
Size [byte]
0
ignore
N/A
0
ignore
N/A
1
Generic SINT Input *
1
51
Generic SINT Output *
1
2
Generic INT Input *
2
52
Generic INT Output *
2
3
Generic DINT Input *
4
53
Generic DINT Output *
4
4
2B0B/0 Freq Setpoint Hz
2
54
2946/1 Trq Mode Hi Spd
4
5
2D40/4 Device Load Act.
2
55
2946/2 Trq Mode Lo Spd
4
6
2D4F/0 Motor i2t utiliz.
2
56
4008/1 NetWordIN1
2
7
2D82/0 Motor voltage
4
57
4008/2 NetWordIN2
2
8
2D88/0 Motor current
2
58
4008/3 NetWordIN3
2
9
2DA2/1 Effective Power
4
59
4008/4 NetWordIN4
2
10
2DA2/2 Apparent Power
4
60
400B/1 AC Drv Ctrl Word
2
11
2DA3/1 Energy Out Motor
4
61
400B/2 C0135 Ctrl Word
2
12
2DA3/2 Energy Out Gen.
4
62
400B/3 Net Spd Stpnt Hz
2
13
2DA4/1 Anlg In1 %
2
63
400B/4 Net Spd Stpnt RPM
2
14
2DA4/2 Anlg In1 Freq
2
64
400B/5 Net Spd 0.01 Hz
2
15
2DA4/3 Anlg In1 PidVal
2
65
400B/6 NetSpdSign 0.1Hz
2
16
2DA4/4 Anlg In1 TorqVal
2
66
400B/7 Net PID Stpnt
2
17
2DA5/1 Anlg In2 %
2
67
400B/8 Net Torque Stpnt
2
18
2DA5/2 Anlg In2 Freq
2
68
6040/0 Control Word
2
19
2DA5/3 Anlg In2 PidVal
2
69
6042/0 Target Velocity
2
20
2DA5/4 Anlg In2 TorqVal
2
70
6046/1 Velocity Min
4
21
2DAA/1 AO1 Value (VDC)
2
71
6046/2 Velocity Max
4
22
2DAA/2 AO1 Value (IDC)
2
72
6048/1 Delta Speed
4
24
2DD3/1 Speed set
4
73
6048/2 Delta Time
2
26
2DDD/0 Actual Frequency
2
74
6049/1 Delta Speed
4
27
400A/1 NetWordOUT1
2
75
6049/2 Delta Time
2
28
400A/2 NetWordOUT2
2
76
6060/0 402 Control Modes
1
29
400C/1 AC Drv Stat Word
2
77
6071/0 402 Target Torque
2
30
400C/2 C0150 Stat Word
2
78
6080/0 Motor Max Speed
4
31
400C/3 Actual Speed Hz
2
79
60E0/0 Pos Torque Limit
2
32
400C/4 Actual Speed RPM
2
80
60E1/0 Neg Torque Limit
2
33
400C/5 Drive State
2
82
400B/13 Process Input Freq.
2
34
400C/6 Act Speed 0.01Hz
2
35
400C/7 Actual Torque Scaled
2
* Selection can be used to specify only the data size of the parameters in the PLC (Scanner). The desired parameters with the corresponding data size can then be assigned manually for the inverter (Adapter) in the »EASY Starter«:
"Settings" tab
à
Overview
à
Fieldbus EtherNet/IP
à
Mapping fieldbus data
 
Data format of the parameters: Parameter attribute list
36
400D/0 Scaled Speed
2
37
401F/1 Actual PID Stpnt
2
38
401F/2 Actual PID Fbk
2
39
401F/3 PID bits
1
40
603F/0 Current Fault
2
41
6041/0 Status Word
2
42
6043/0 Velocity Demand
2
43
6044/0 Velocity Actual
2
44
6061/0 402 Mode Display
1
45
6077/0 402 ActualTorq %
2
46
6078/0 402 ActualCur %
2
47
6079/0 402 DClink Volt
4
48
60FD/0 Dig Inputs Stat
4
50
400C/9 Process Output Freq.
2
 
Assembly output objects (outputs)
Assembly output objects are usually used to enable the inverter (Adapter) and specify a speed or torque setpoint.
Depending on the data length defined by the PLC (Scanner), the memory image of the I/O data can vary in size.
Assembly output objects are assumed to have a 32-bit Run/Idle header. When mapping assemblies, this header is automatically inserted into the data flow by most Allen-Bradley PLC/SLC devices. This does not require any adaptations.
If your PLC does not support the 32-bit Run/Idle header, add a leading 32-bit header to the output image. Set the data in the header to 0.
Bit 0 of the header can be defined in the process image of your PLC:
–
Status 0: Idle mode
 
–
Status 1: Run mode
 
Structure of the output objects
Attribute
(Instance ID)
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
20
(0x14)
0
FaultRst
RunFwd (CW)
1
2
Speed Reference (low byte)
3
Speed Reference (high byte)
21
(0x15)
0
NetRef
NetCtrl
FaultRst
RunRev (CCW)
RunFwd (CW)
1
2
Speed Reference (low byte)
3
Speed Reference (high byte)
22
(0x16)
0
FaultRst
RunFwd (CW)
1
2
Speed Reference (low byte)
3
Speed Reference (high byte)
4
Torque Reference (low byte)
5
Torque Reference (high byte)
23
(0x17)
0
NetRef
NetCtrl
FaultRst
RunRev (CCW)
RunFwd (CW)
1
2
Speed Reference (low byte)
3
Speed Reference (high byte)
4
Torque Reference (low byte)
5
Torque Reference (high byte)
110
(0x6E)
0
...
31
Custom Output
If the assembly output objects 20 or 22 are used for control and reference, NetCtrl and NetRef must be set accordingly by explicitly accessing 0x29-Control Supervisor Object, attribute 5 (NetCtrl) and 0x2A-AC Drive Object, attribute 2 (NetRef).
 
 
Assembly input objects (inputs)
Assembly input objects are usually used to monitor the status of the inverter (Adapter) and to query current actual values (e.g. the current speed).
The input objects are mapped in the Adaptermemory from byte 0 and transmitted "modeless".
The inverter does not use a 32-bit header for the real time status. Thus, the start address in the assembly memory map is the real start of the first assembly data element.
Note the actual assembly lengths when mapping the assembly input objects to the control memory.
 
Structure of the input objects
Attribute
(Instance ID)
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
70
(0x46)
0
Running1
(Fwd, CW)
Faulted
1
2
Speed Actual (low byte)
3
Speed Actual (high byte)
71
(0x47)
0
AtReference
RefFromNet
CtrlFromNet
Ready
Running2
(Rev, CCW)
Running1
(Fwd, CW)
Warning
Faulted
1
Drive State
2
Speed Actual (low byte)
3
Speed Actual (high byte)
72
(0x48)
0
Running1
(Fwd, CW)
Faulted
1
2
Speed Actual (low byte)
3
Speed Actual (high byte)
4
Torque Actual (low byte)
5
Torque Actual (high byte)
73
(0x49)
0
AtReference
RefFromNet
CtrlFromNet
Ready
Running2
(Rev, CCW)
Running1
(Fwd, CW)
Warning
Faulted
1
Drive State
2
Speed Actual (low byte)
3
Speed Actual (high byte)
4
Torque Actual (low byte)
5
Torque Actual (high byte)
111
(0x6F)
0
...
31
Custom Input