0x29-Control Supervisor Object

The "Control Supervisor Object" describes all management functions of the device for the motor control.
Instance attributes
Attribute ID
Name
Info / parameter
3
Run1
AC drive control word 0x400B:001 (P592.01): Bit 0 (run forward, CW)
4
Run2
AC drive control word 0x400B:001 (P592.01): Bit 1 (run reverse, CCW)
5
NetCtrl
AC Drive control word 0x400B:001 (P592.01): Bit 5 (activate network control: 0x2631:037 (P400.37) = 114)
6
State
AC drive status word 0x400C:001 (P593.01):
Bits 8 ... 11 (profile status/Drive State)
Bits 12 ... 15 masked
7
Running1
AC drive status word 0x400C:001 (P593.01): Bit 2 (run forward active, CW)
8
Running2
AC drive status word 0x400C:001 (P593.01): Bit 3 (run reverse active, CCW)
9
Ready
AC drive status word 0x400C:001 (P593.01): Bit 4 (ready)
10
Faulted
AC drive status word 0x400C:001 (P593.01): Bit 0 (fault/trouble active)
11
Warning
AC drive status word 0x400C:001 (P593.01): Bit 1 (warning active)
12
FaultRst
AC drive control word 0x400B:001 (P592.01): Bit 2 (error reset)
13
FaultCode
Error code 0x603F (P150.00)
15
CtrlFromNet
AC drive status word 0x400C:001 (P593.01): Bit 5 (network control active)
Assignment of "CiA 402 plus States" to ""AC Drive Profile Drive States"
CiA 402 plus States
AC Drive Profile Drive States
START (0)
0: Manufacturer-specific
NOT_READY_TO_SWITCH_ON (2)
1: Startup (drive initialization)
SWITCH_ON_DISABLED (3)
2: Not_Ready (mains voltage switched off)
READY_TO_SWITCH_ON (4)
3: Ready (mains voltage switched on)
SWITCHED_ON (5)
OPERATION_ENABLED (6)
4: Enabled (drive has received run command)
DISABLE_OPERATION (7)
5: Stopping (drive has received stop command and is stopped)
SHUT_DOWN (8)
QUICK_STOP (9)
FAULT_REACTION_ACTIVE (10)
6: Fault_Stop (drive is stopped due to a fault)
FAULT (11)
7: Faulted (faults have occurred)