Master value sources

Source of the master value
When changing the parameter, the inverter must be inhibited. Disable operation
 
The master values for the technology application come from a variety of sources. The source is selected via the Master value source parameter. 0x5020:014
The following sources can be selected:
–
System bus
 
–
Load encoder
 
–
Virtual master
 
–
Analog input 1
 
 
Fig. 1: Selection of the master value source
 
Parameter
Address
Name / setting range / [default setting]
Information
0x5020:014
Master value source
–
Setting can only be changed if the inverter is disabled.
 
0
System bus
The system bus provides the external master velocity value.
1
Load encoder
The signal from the load encoder interface is taken as the master velocity value.
2
Virtual master
The virtual master, whose setpoint velocity comes from the Set virtual master velocity PDO, serves as master value master. 0x5045:011
3
Analog input 1