Detection of changed settings of the feedback system

Bit 8 of status word 2 is used to indicate whether a change has been made to the settings of the feedback system since the Not ready to switch on state was exited. When a change is made, bit 0 is set to the value "1". 0x2833
When switching to the Operation enabled state, bit 8 is reset to the value "0".
In all device states, monitoring of changes to the following parameters remains active.
 
Relevant parameters of other functions
Address
Name
Default setting
Setting range
Load encoder/master encoder type
SinCos encoder [1]
Selection list
Load encoder/master encoder settings (HIPERFACE®): Type code manual input
0
0 ... 255
Load encoder/master encoder settings (HIPERFACE®): Manual input - Number of detectable load/master encoder revolutions
1
1 ... 65535
Load encoder/master encoder settings (HIPERFACE®): Serial number
- (Read only)
Load encoder/master encoder settings (encoder): Increments/revolution
1024
1 ... 262143
Position encoder resolution: Encoder increments
16 bit [65536]
Selection list
Position encoder resolution: Motor revolutions
1
1 ... 1