Status LEDs
The "MS" LED indicate the CIP module status.
|
LED "MS" (green/red)
|
CIP module status
|
Status/meaning
|
|
off
|
Nonexistent
|
The network option is not supplied with voltage.
|
|
On (green)
|
Operational
|
The network option works correctly.
|
|
Blinking green
|
Standby
|
The network option is not configured completely or the configuration is incorrect.
|
|
Blinking red
|
Major recoverable fault
|
The network option contains a correctable error.
|
|
on (red)
|
Major unrecoverable fault
|
The network option contains a non-correctable error.
|
|
Blinking green/red
|
Device self testing
|
The network option executes a self-test.
|
The "NS" LED indicate the CIP network status.
|
LED "NS" (green/red)
|
CIP network status
|
Status/meaning
|
|
off
|
No IP address
|
The network option is not supplied with voltage or has not received an IP address yet.
|
|
On (green)
|
Connected
|
The network option works correctly and has established a connection to the scanner.
|
|
Blinking green
|
No connections
|
The network option
–
works correctly,
–
has been assigned to an IP address,
–
has not been implemented into the network yet by the scanner.
|
|
Blinking red
|
Connection timeout
|
A time-out has occurred.
|
|
on (red)
|
Duplicate IP
|
The network option cannot access the network (IP address conflict).
|
|
Blinking green/red
|
Device self testing
|
The network option executes a self-test.
|
Status displays at the RJ45 sockets
The LEDs at the RJ45 sockets indicate the connection status to the network:
|
LED "Link" (green)
|
Status/meaning
|
|
off
|
No connection to the network.
|
|
on
|
A physical connection to the network is available.
|
|
LED "Activity" (yellow)
|
Status/meaning
|
|
off
|
No data transfer.
|
|
on or flickers
|
Data is exchanged via the network.
|