Pole position identification (PPI) 360°

NOTICE
Mechanical damage of the motor caused by hanging loads!
Possible consequences: Irreversible damage of the motor.
▶
The motor must not be braked or blocked during the pole position identification. Thus, this function must not be used for hanging loads!
 
 
 
NOTICE
Thermal overload of the motor!
The motor may be permanently damaged.
▶
Before executing the pole position identification, check that the following monitoring systems are parameterised correctly.
 
▶
 
▶
 
 
 
NOTICE
▶
 
 
 
Functional description
 
If the servo control is set for synchronous motor and no error is pending, the current is first raised in a ramp-shaped manner to 141 % of the rated motor current after the inverter is enabled.
 
Left image
First, the rotor is moved from any position of rest to the 0° angle.
–
For this purpose, the amplitude of the d current vector is created in the stator coordinate system at a starting angle of 45° and then turned to 0°.
 
–
A sufficiently high amplitude of the d current vector and its rotary motion result in a magnetic force that moves the rotor to the angle 0°.
 
 
Right image
Afterwards, the d current vector is turned further in 15 steps by 22.5° each starting at the angle 0°.
–
Due to the magnetic forces, the rotor adjusts to the respective angle.
 
–
After 16 steps, the rotor has moved by absolute electrical 360°.
 
 
Result
For determining the pole position, a mean value is calculated from all 16 messages. The rotor displacement angle can be recorded via the 0x2DDE parameter (actual motor rotor angle position). The detected pole position is stored in the inverter parameters , 0x2C03:0020x2C03:004. The detected pole position must then be saved.
 
Abort of the pole position identification
The pole position identification is aborted if the deviations between the rotary motion of the current vector and the rotor exceed the fault tolerance set in 0x2C41:004
(check if parameter is available)
.
 
Preconditions for the performance
–
The motor must not be braked or blocked during the pole position identification.
 
–
The servo inverter is error-free and in Switched on device state.
 
 
Response of the motor during performance
The rotor aligns during the pole position identification. The motor shaft moves by max. one electrical revolution which causes a corresponding movement of the connected mechanics!
 
How to execute the pole position identification PLI (360°):
1.
If the servo inverter is enabled, disable it.Enable operation
 
2.
Set the object 0x2825 to "5" to change to the "pole position identification PLI (360°)" operating mode.
 
3.
Before the PLI can be started, the works mentioned below must be completed.
 
4.
Enable the servo inverter to start the pole position identification (360°). Note: Inhibiting the controller serves to abort the started procedure any time if required without changing the settings.
 
 
After the pole position identification has been completed successfully...
...the controller is inhibited automatically and the pole position determined for the activated feedback system is set in the 0x2C03:002 object.
–
Save the changed settings.
The »EASY Starter« serves to save the parameter settings of the servo inverter as parameter file (*.gdc). Saving the parameter settings
 
–
The inverter disable set automatically by the procedure can be deactivated again via the CiA402 control word 0x6040. Enable operation
 
 
Adapt pole position identification PLI (360°)
Fig. 1: Chronological sequence of the pole position identification
 
A Start of the pole position identification 
 
 
B End of the pole position identification 
 
 
1 Current position of the rotor 
 
 
2 Commutation angle of current vector, variable of the motor control 
 
 
3 Amplitude of the d current vector 
 
 
4 Amplitude of the q current vector 
 
 
①
Structure of the d current vector at electrical 45° (starting angle) 
 
 
②
Angular change of the d current vector to electrical 0°; alignment of the rotor 
 
 
③
15 angular changes by 22.5° each and subsequent plausibility check 
 
 
In case of drives with a high static friction, mass inertia or alternating load, an optimisation may be necessary:
–
The amplitude of the current vector must be set so high that the motor with a high mass inertia can be accelerated.
 
–
The cyclic continued rotation of the current vector by 22.5° has to cause an equivalent angular rotation of the motor shaft (rotor). A step function has to be achieved. Here, actual positions with very low overshoots are visible.
 
 
NOTICE
Thermal overload of the motor!
The motor may be permanently damaged.
▶
If no temperature monitoring is available in the motor, and/or the I²xt motor monitoring and the maximum current monitoring are not parameterised correctly, the motor can be permanently damaged if the current amplitude is set too high!
 
▶
 
▶
 
 
 
Overview of more objects available for
–
Identification
 
–
Triggering
 
–
Diagnostics
 
 
Tip!
An oscilloscope serves to execute the optimisation
 
Parameter
Subindex
Value/unit
 INFO
0
CiA402 mode active [0]
Operating modes [5] for PLI 360°
0x2824
0
Off [0], On [1]
0
0x0000
Simulation of the CiA state machine
0
100
Progress bar
1
100 %
PLI(360°) current amplitude
2
40 s
PLI(360°) ramp time
3
Field: clockwise [0]
PLI(360°) direction of rotation
4
20°
PLI(360°) fault tolerance
5
4.81 A
Display
2
-90.0°
Detected pole position values
4
0.0°
0
1850
current rotor angle
2
0.03 A
Phase U current
3
0.04 A
Phase V current
4
-0.01 A
Phase W current
3
0.00 A
Setpoint D current
1
0.01 A
Current D current
0
150.0 %
Max current
0
3.400 A
Motor rated current, reference for 0x2C61:1
1
16.5 A
Overcurrent monitoring: threshold
1
5.00 A
User info regarding rated current
2
10.00 A
User info regarding maximum current
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2C61:001
Pole position identification (360°) settings: Current amplitude
1 ... [71] ... 1000 %
–
Setting can only be changed if the inverter is disabled.
 
Percentage adaptation of the current amplitude.
–
For large machines and high mass inertia values or for linear direct drives, the current amplitude usually must be increased.
 
–
Default setting 100 % ≡ 141 % of Rated motor current (0x6075)
 
Note!
If the current amplitude is set to >  100  %, the device utilisation (Ixt) monitoring and/or one of the motor monitoring functions may respond and cause the abort of the pole position identification.
0x2C61:002
Pole position identification (360°) settings: Ramp time
1 ... [40] ... 600 s
–
Setting can only be changed if the inverter is disabled.
 
Percentage adaptation of the ramp time.
–
For large machines and high mass inertia values, the ramp time must be increased.
 
–
For small machines, however, the pole position identification can be accelerated by reducing the ramp time.
 
0x2C61:003
Pole position identification (360°) settings: Direction of rotation
–
Setting can only be changed if the inverter is disabled.
 
Selection of travel direction.
In some situations, it may be helpful to reverse the travel direction for the pole position identification (e. g. for linear motor at the end stop).
0
CW
1
CCW
2
CW + CCW
3
CCW + CW
0x2C61:004
Pole position identification (360°) settings: Error tolerance
15 ... [20] ... 50 °
Setting of the fault tolerance for the plausibility check.
–
If the rotor position detected via the encoder system is not within the tolerance zone around the position that is output in a controlled manner, the pole position identification is aborted and the parameterised error response is tripped.
 
0x2C61:005
Pole position identification (360°) settings: Absolute current amplitude
–
Read only: x.xx A
 
Display of the absolute current amplitude.
0x2C61:006
Pole position identification (360°) settings: ixt threshold for reversal of rotating direction
0 ... [30] ... 100 %
0x2C61:010
Pole position identification (360°) settings: Actual commutation angle
–
Read only: x.xxx °