Process data transfer

Process data objects (PDOs) are used for the cyclic transmission of (process) data via CANopen. PDOs only contain data and an identifier. They do not contain any information about the sender or receiver and are therefore very efficient.
 
Details
–
Four process data channels (PDO1 ... PDO4) are available.
 
–
Process data objects which the inverter receives via the network are referred to as "Receive PDOs" (RPDOs).
 
–
Process data objects which the inverter sends via the network are referred to as "Transmit PDOs" (TPDOs).
 
–
The maximum length of a PDO is 8 bytes (4 data words).
 
–
Each PDO requires a unique identifier ("COB-ID") for the purpose of identification within the network.
 
–
Communication parameters (such as the transmission type and cycle time) for each PDO can be set freely and independently of the settings of other PDOs
 
–
Default setting:
 
–
RPDO1 and TPDO1 are activated.
 
–
RPDO2 ... RPDO4 and TPDO2 ... TPDO4 are deactivated.
 
 
–
The respective mapping cannot be changed.
 
 
Set RPDO
How to change the communication parameters for RPDO1:
1.
Set RPDO1 to “invalid": RPDO1 - COB-ID 0x2304:041, Bit31 = 1.
 
2.
If appropriate, change timeout time: RPDO1 - Event timer 0x2304:045.
Default setting: 100 ms
 
3.
If necessary, change the transmission of the process data: RPDO1 - Transmission type 0x2304:042.
Default setting: 255 (cyclic or event-controlled)
 
4.
If appropriate, change identifier and reset RPDO1 to "valid" (bit31 = “0”): RPDO1 - COB-ID 0x2304:041.
Default setting: Identifier = basic identifier (0x200) + node address (hex)
Example: Node address = 10 (0xA)
Identifier = 0x200 + 0xA = 0x0000020A
 
RPDO1 is enabled again with the new settings.
 
Set TPDO
How to change the communication parameters for TPDO1:
1.
Set TPDO1 to “invalid": TPDO1 - COB-ID 0x2304:081, Bit31 = 1.
 
2.
If required, change timeout: TPDO1 - Event timer 0x2304:085.
Default setting: 20 ms
 
3.
If necessary, change the transmission of the process data: TPDO1 - Transmission type 0x2304:082.
Default setting: 255 (cyclic)
 
4.
If required, Change identifier and reset TPDO1 to "valid" (bit31 = “0”): TPDO1 - COB-ID 0x2304:081.
Default setting: Identifier = basic identifier (0x40000180) + node address (hex)
Example: Node address = 10 (0xA)
Identifier = 0x40000180 + 0xA = 0x4000018A
 
TPDO1 is enabled again with the new settings.
 
Transmission type
Process data objects are transmitted event-controlled or time-controlled. Combinations of the different transmission types are also possible:
–
Event-controlled: The PDO is sent when a special device-internal event has occurred, e.g. change of the data content of the TPDO or expiry of a transmission cycle time.
 
–
Synchronous: After the inverter has received a sync telegram (COB-ID 0x80), it sends a TPDO or receives an RPDO.
 
–
Cyclic: The PDOs are transmitted cyclically after the transmission cycle time has elapsed.
 
–
Via RTR (TPDO only): Another device triggers the transmission of a TPDO with a request via a data request telegram RTR (Remote Transmit Request). For this purpose, the data requestor (e.g. master) sends an RTR with the COB ID of the TPDO that is to be requested to transmit. The receiver detects the RTR and transmits.
 
 
Transmission type
PDO transmission
Description
0
Synchronous and acyclic
–
The PDO is transmitted event-controlled with a sync if the PDO data has changed.
 
1 ... 240
Synchronous and cyclic
–
Selection n = 1: The PDO is transmitted with every sync.
 
–
Selection 1 < n ≤ 240: The PDO is transmitted at every nth sync.
 
241 ... 251
-
Reserved
252 (only TPDO)
Synchronous - RTR only
–
A sync request from the sync master updates the TPDO.
 
–
The TPDO is not sent until it receives an RTR request.
 
253 (only TPDO)
Asynchronous - RTR only
–
The TPDO is updated when a change is made.
 
–
The TPDO is not sent until it receives an RTR request.
 
254
Asynchronous and cyclic
–
The PDO is sent and received in the set cycle time.
 
–
Changing the PDO data has no effect.
 
255
Asynchronous and cyclic OR acyclic
–
The PDO is sent and received in the set cycle time.
 
–
In addition, PDO data is sent and received each time it is changed.
 
–
The PDO is event-controlled and transmitted cyclically.
 
 
Synchronization of PDOs with sync telegram
With cyclic transmission, one or more PDOs are sent or received at fixed time intervals. For the synchronization of the cyclic process data the special "Sync telegram" is used.
–
The sync telegram is the trigger for transmitting process data from the slaves to the master and for transferring process data from the master to the slaves.
 
–
The response to a sync telegram is determined by the transmission type selected.
 
Set up sync telegram:
–
Specify identifier:
 
–
All inverters are set to the sync telegram with identifier 0x80 according to CANopen specification.
 
–
If sync telegrams are only to be received by specific nodes, their identifiers can be specified with a value of up to and including 0x07FF.
 
–
The identifier may only be changed if the inverter does not send any sync telegrams (0x2304:001, Bit 30 = "0").
 
 
–
Generate sync telegram:
 
–
Activate transmission: 0x2304:001, Bit 30 = 1
 
–
Set transmission cycle: 0x2304:002
 
 
Sync telegram assignment
8. Byte (data 4)
7. Byte (data 3)
6. Byte (data 2)
5. Byte (data 1)
Bit 31
Bit 30
Bit 29 ... Bit 11
Bit 10 ... Bit 0
x
0/1
Extended Identifier (not supported)
Bit 29 ... Always set bit 11 to "0".
11-bit identifier
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2301:006
CANopen settings: COB-ID Configuration - PDO
Selection of the process for assigning the identifiers.
Irrespective of this selection, these are the following bits of the identifiers:
–
Bit 30: "RTR not allowed" (only in case of TPDO)
 
–
Bit 31: "PDO invalid"
 
0
Base + node-ID
Identifier = set (basic) identifiers + set node address
1
Freely configurable
Identifier = set identifiers
2
Legacy base + node ID
Identifier = inherited (basic) identifier + set node address
0x2304:001
CANopen settings: SYNC - COB-ID
0x00000000 ... [0x00000080] ... 0xFFFFFFFF
Identifier for sync telegram.
Image of the CANopen object 0x1005
How to change the identifier:
1.
Deactivate Sync: Set bit 30 to "0".
 
2.
Change identifier.
 
3.
Activate Sync: Set bit 30 to "1".
 
Bit  0
COB-ID bit 0
Bit  1
COB-ID bit 1
Bit  2
COB-ID bit 2
Bit  3
COB-ID bit 3
Bit  4
COB-ID bit 4
Bit  5
COB-ID bit 5
Bit  6
COB-ID bit 6
Bit  7
COB-ID bit 7
Bit  8
COB-ID bit 8
Bit  9
Bit  10
COB-ID bit 10
Identifier for sync telegram.
Image of the CANopen object 0x1005
How to change the identifier:
1.
Deactivate Sync: Set bit 30 to "0".
 
2.
Change identifier.
 
3.
Activate Sync: Set bit 30 to "1".
 
Bit  30
Enable sync
Bit  31
COB-ID bit 31 (reserved)
0x2304:002
CANopen settings: Communication cyclic period
0 ... [0] ... 65535000
Display of the identifier for emergency telegrams.
Image of the CANopen object 0x1006
0x2304:041
CANopen settings: RPDO1 - COB-ID
0x00000000 ... [0x00000201] ... 0xFFFFFFFF
RPDO1: identifier
Image of the CANopen object 0x1400:001
How to change the identifier:
1.
Set PDO to "invalid": Set bit 31 to "1".
 
2.
Change identifier and reset PDO to "valid" (bit 31 = "0").
 
Bit  0
COB-ID bit 0
Bit  1
COB-ID bit 1
Bit  2
COB-ID bit 2
Bit  3
COB-ID bit 3
Bit  4
COB-ID bit 4
Bit  5
COB-ID bit 5
Bit  6
RANLI_C2304_S041_CAN_0000B0006
Bit  7
COB-ID bit 7
RPDO1: identifier
Image of the CANopen object 0x1400:001
How to change the identifier:
1.
Set PDO to "invalid": Set bit 31 to "1".
 
2.
Change identifier and reset PDO to "valid" (bit 31 = "0").
 
Bit  8
COB-ID bit 8
Bit  9
COB-ID bit 9
Bit  10
COB-ID bit 10
Bit  31
PDO invalid
0x2304:042
CANopen settings: RPDO1 - Transmission type
0 ... [255] ... 255
RPDO1: transmission type in compliance with DS301 V4.02
Image of the CANopen object 0x1400:002
0x2304:045
CANopen settings: RPDO1 - Event timer
0 ... [100] ... 65535 ms
RPDO1: time-out for the monitoring of data reception.
Image of the CANopen object 0x1400:005
–
With setting "0" the monitoring is deactivated.
 
0x2304:051
CANopen settings: RPDO2 - COB-ID
0x00000000 ... [0x80000301] ... 0xFFFFFFFF
RPDO2: identifier
Image of the CANopen object 0x1401:001
How to change the identifier:
1.
Set PDO to "invalid": Set bit 31 to "1".
 
2.
Change identifier and reset PDO to "valid" (bit 31 = "0").
 
Bit  0
COB-ID bit 0
Bit  1
COB-ID bit 1
Bit  2
COB-ID bit 2
Bit  3
COB-ID bit 3
Bit  4
COB-ID bit 4
Bit  5
COB-ID bit 5
Bit  6
COB-ID bit 6
Bit  7
COB-ID bit 7
Bit  8
COB-ID bit 8
Bit  9
COB-ID bit 9
Bit  10
COB-ID bit 10
Bit  31
PDO invalid
0x2304:052
CANopen settings: RPDO2 - Transmission type
0 ... [255] ... 255
RPDO2: transmission type in compliance with DS301 V4.02
Image of the CANopen object 0x1401:002
0x2304:055
CANopen settings: RPDO2 - Event timer
0 ... [100] ... 65535 ms
RPDO2: time-out for the monitoring of data reception.
Image of the CANopen object 0x1401:005
–
With setting "0" the monitoring is deactivated.
 
0x2304:061
CANopen settings: RPDO3 - COB-ID
0x00000000 ... [0x80000401] ... 0xFFFFFFFF
RPDO3: identifier
Image of the CANopen object 0x1402:001
How to change the identifier:
1.
Set PDO to "invalid": Set bit 31 to "1".
 
2.
Change identifier and reset PDO to "valid" (bit 31 = "0").
 
Bit  0
COB-ID bit 0
Bit  1
COB-ID bit 1
Bit  2
COB-ID bit 2
Bit  3
COB-ID bit 3
Bit  4
COB-ID bit 4
Bit  5
COB-ID bit 5
Bit  6
COB-ID bit 6
Bit  7
COB-ID bit 7
Bit  8
COB-ID bit 8
Bit  9
COB-ID bit 9
Bit  10
COB-ID bit 10
Bit  31
PDO invalid
0x2304:062
CANopen settings: RPDO3 - Transmission type
0 ... [255] ... 255
RPDO3: transmission type in compliance with DS301 V4.02
Image of the CANopen object 0x1402:002
0x2304:065
CANopen settings: RPDO3 - Event timer
0 ... [100] ... 65535 ms
RPDO3: time-out for the monitoring of data reception.
Image of the CANopen object 0x1402:005
–
With setting "0" the monitoring is deactivated.
 
0x2304:071
CANopen settings: RPDO4 - COB-ID
0x00000000 ... [0x80000501] ... 0xFFFFFFFF
RPDO4: Identifier
Image of the CANopen object 0x1403:001
How to change the identifier:
1.
Set PDO to "invalid": Set bit 31 to "1".
 
2.
Change identifier and reset PDO to "valid" (bit 31 = "0").
 
Bit  0
COB-ID bit 0
Bit  1
COB-ID bit 1
Bit  2
COB-ID bit 2
Bit  3
COB-ID bit 3
Bit  4
COB-ID bit 4
Bit  5
COB-ID bit 5
Bit  6
COB-ID bit 6
Bit  7
COB-ID bit 7
Bit  8
COB-ID bit 8
Bit  9
COB-ID bit 9
Bit  10
COB-ID bit 10
Bit  31
PDO invalid
0x2304:072
CANopen settings: RPDO4 - Transmission type
0 ... [255] ... 255
RPDO4: Transmission type in compliance with DS301 V4.02
Image of the CANopen object 0x1403:002
0x2304:075
CANopen settings: RPDO4 - Event timer
0 ... [100] ... 65535 ms
RPDO4: Timeout for monitoring data reception.
Image of the CANopen object 0x1403:005
–
With setting "0" the monitoring is deactivated.
 
0x2304:081
CANopen settings: TPDO1 - COB-ID
0x00000000 ... [0x40000181] ... 0xFFFFFFFF
TPDO1: identifier
Image of the CANopen object 0x1800:001
How to change the identifier:
1.
Set PDO to "invalid": Set bit 31 to "1".
 
2.
Change identifier and reset PDO to "valid" (bit 31 = "0").
 
Bit  0
COB-ID bit 0
Bit  1
COB-ID bit 1
Bit  2
COB-ID bit 2
Bit  3
COB-ID bit 3
Bit  4
COB-ID bit 4
Bit  5
COB-ID bit 5
Bit  6
COB-ID bit 6
Bit  7
COB-ID bit 7
Bit  8
COB-ID bit 8
Bit  9
COB-ID bit 9
Bit  10
COB-ID bit 10
Bit  30
RTR not allowed
Bit  31
PDO invalid
0x2304:082
CANopen settings: TPDO1 - Transmission type
0 ... [255] ... 255
TPDO1: transmission type in compliance with DS301 V4.02
Image of the CANopen object 0x1800:002
0x2304:083
CANopen settings: TPDO1 - Inhibit time
0.0 ... [0.0] ... 6553.5 ms
TPDO1: minimum time between the transmission of two identical PDOs in compliance with DS301 V4.02
Image of the CANopen object 0x1800:003
–
The set time is rounded off internally to whole ms.
 
0x2304:085
CANopen settings: TPDO1 - Event timer
0 ... [20] ... 65535 ms
TPDO1: Cycle time for PDO transmission with transmission type "254" or "255".
Image of the CANopen object 0x1800:005
0x2304:091
CANopen settings: TPDO2 - COB-ID
0x00000000 ... [0xC0000281] ... 0xFFFFFFFF
TPDO2: identifier
Image of the CANopen object 0x1801:001
How to change the identifier:
1.
Set PDO to "invalid": Set bit 31 to "1".
 
2.
Change identifier and reset PDO to "valid" (bit 31 = "0").
 
Bit  0
COB-ID bit 0
Bit  1
COB-ID bit 1
Bit  2
COB-ID bit 2
Bit  3
COB-ID bit 3
Bit  4
COB-ID bit 4
Bit  5
COB-ID bit 5
Bit  6
COB-ID bit 6
Bit  7
COB-ID bit 7
Bit  8
COB-ID bit 8
Bit  9
COB-ID bit 9
Bit  10
COB-ID bit 10
Bit  30
RTR not allowed
Bit  31
PDO invalid
0x2304:092
CANopen settings: TPDO2 - Transmission type
0 ... [255] ... 255
TPDO2: transmission type in compliance with DS301 V4.02
Image of the CANopen object 0x1801:002
0x2304:093
CANopen settings: TPDO2 - Inhibit time
0.0 ... [0.0] ... 6553.5 ms
TPDO2: minimum time between the transmission of two identical PDOs in compliance with DS301 V4.02
Image of the CANopen object 0x1801:003
–
The set time is rounded off internally to whole ms.
 
0x2304:095
CANopen settings: TPDO2 - Event timer
0 ... [0] ... 65535 ms
TPDO2: Cycle time for PDO transmission with transmission type "254" or "255".
Image of the CANopen object 0x1801:005
0x2304:101
CANopen settings: TPDO3 - COB-ID
0x00000000 ... [0xC0000381] ... 0xFFFFFFFF
TPDO3: identifier
Image of the CANopen object 0x1802:001
How to change the identifier:
1.
Set PDO to "invalid": Set bit 31 to "1".
 
2.
Change identifier and reset PDO to "valid" (bit 31 = "0").
 
Bit  0
COB-ID bit 0
Bit  1
COB-ID bit 1
Bit  2
COB-ID bit 2
Bit  3
COB-ID bit 3
Bit  4
COB-ID bit 4
Bit  5
COB-ID bit 5
Bit  6
COB-ID bit 6
Bit  7
COB-ID bit 7
Bit  8
COB-ID bit 8
Bit  9
COB-ID bit 9
Bit  10
COB-ID bit 10
Bit  30
RTR not allowed
Bit  31
PDO invalid
0x2304:102
CANopen settings: TPDO3 - Transmission type
0 ... [255] ... 255
TPDO3: transmission type in compliance with DS301 V4.02
Image of the CANopen object 0x1802:002
0x2304:103
CANopen settings: TPDO3 - Inhibit time
0.0 ... [0.0] ... 6553.5 ms
TPDO3: minimum time between the transmission of two identical PDOs in compliance with DS301 V4.02
Image of the CANopen object 0x1802:003
–
The set time is rounded off internally to whole ms.
 
0x2304:105
CANopen settings: TPDO3 - Event timer
0 ... [0] ... 65535 ms
TPDO3: Cycle time for PDO transmission with transmission type "254" or "255".
Image of the CANopen object 0x1802:005
0x2304:111
CANopen settings: TPDO4 - COB-ID
0x00000000 ... [0xC0000481] ... 0xFFFFFFFF
TPDO4: Identifier
Image of the CANopen object 0x1803:001
How to change the identifier:
1.
Set PDO to "invalid": Set bit 31 to "1".
 
2.
Change identifier and reset PDO to "valid" (bit 31 = "0").
 
Bit  0
COB-ID bit 0
Bit  1
COB-ID bit 1
Bit  2
COB-ID bit 2
Bit  3
COB-ID bit 3
Bit  4
COB-ID bit 4
Bit  5
COB-ID bit 5
Bit  6
COB-ID bit 6
Bit  7
COB-ID bit 7
Bit  8
COB-ID bit 8
Bit  9
COB-ID bit 9
Bit  10
COB-ID bit 10
Bit  30
RTR not allowed
Bit  31
PDO invalid
0x2304:112
CANopen settings: TPDO4 - Transmission type
0 ... [255] ... 255
TPDO4: Transmission type in compliance with DS301 V4.02
Image of the CANopen object 0x1803:002
0x2304:113
CANopen settings: TPDO4 - Inhibit time
0.0 ... [0.0] ... 6553.5 ms
TPDO4: Minimum time between the transmission of two identical PDOs according to DS301 V4.02
Image of the CANopen object 0x1803:003
–
The set time is rounded off internally to whole ms.
 
0x2304:115
CANopen settings: TPDO4 - Event timer
0 ... [0] ... 65535 ms
TPDO4: Cycle time for PDO transmission with transmission type "254" or "255".
Image of the CANopen object 0x1803:005