Supported CANopen objects

The inverter can be parameterized with Lenze parameters as well as with the manufacturer-independent "CANopen objects". For fully CANopen-compliant communication, only the CANopen objects may be used for parameterization.
The CANopen objects described here are defined in the CANopen specification DS301, V4.02. The mapping to Lenze parameters is listed in the following table in the "Info" column.
 
 
Supported CANopen objects
Address
Name / setting range / [default setting]
Information
0x1000
Device type
–
Read only
 
CANopen device profile according to CANopen specification CiA 301/CiA 402
Specifies the type of axis: 0x01020000 = Servo single axis
0x1001
Error register
–
Read only
 
Bit-coded error status.
–
Bit 0 is set if an error is active.
 
0x1003
Pre-defined error field
Error list display
0x1003:000
Pre-defined error field: Number of errors
–
Read only
 
Number of errors
0x1003:001
...
0x1003:010
Pre-defined error field: Standard error field 1
...
Pre-defined error field: Standard error field 10
–
Read only
 
Error messages
–
The error messages (U32) consist of a 16-bit error code and a 16-bit manufacturer-specific information field.
 
0x1005
COB-ID SYNC
0x00000000 ... [0x00000080] ... 0xFFFFFFFF
Identifier for sync telegram
–
See Lenze image: 0x2304:001
 
0x1006
Communication cyclic period
0 ... [0] ... 65535000 µs
Cycle time for sync telegrams
–
See Lenze image: 0x2304:002
 
0x1008
Manufacturer device name
–
Read only
 
Display of the manufacturer device name
0x1009
Manufacturer hardware version
–
Read only
 
Display of the manufacturer hardware version of the CANopen module
0x100A
Manufacturer software version
–
Read only
 
Display of the manufacturer software version
0x1014
COB-ID Emergency telegram (EMCY)
–
Read only
 
Display of the identifier for emergency telegrams
–
See Lenze image: 0x2302:003
 
0x1015
Inhibit time EMCY
Blocking time which can be set in order to limit the bus load in the case of emergency telegrams following quickly in succession.
–
See Lenze image: 0x2304:003
 
0x1016
Consumer heartbeat time
Node ID and heartbeat time of the max. 4 nodes to be monitored
–
See Lenze image: 0x2304:004
 
–
See Lenze image: 0x2304:005
 
–
See Lenze image: 0x2304:006
 
–
See Lenze image: 0x2304:007
 
0x1017
Producer heartbeat time
Time interval for the transmission of the heartbeat telegram to the consumer(s).
–
See Lenze image: 0x2304:020
 
0x1018
Identity object
Inverter data
0x1018:001
Identity object: Vendor ID
–
Read only
 
Manufacturer's identification number
Lenze = 0x0000003B
0x1018:002
Identity object: Product ID
–
Read only
 
Inverter product code
0x1018:003
Identity object: Revision number
–
Read only
 
Main and subversion of the firmware
0x1018:004
Identity object: Serial number
–
Read only
 
Serial number of the inverter
0x1029
Error behavior
Behavior in case of communication errors
0x1029:001
Error behavior: Communication error
Selection to which NMT state the inverter is to change automatically in the event of a communication error.
–
See Lenze image: 0x2304:021
 
0x1200
SDO1 server parameter
Setting the identifiers for the SDO server channel 1
0x1200:001
SDO1 server parameter: COB-ID client > server (rx)
Specification of the receive identifier for SDO server channel 1.
–
Identifier = node address 0x2302:001 + 0x600 (cannot be changed)
 
0x1200:002
SDO1 server parameter: COB-ID server > client (tx)
Specification of the transmit identifier for SDO server channel 1.
–
Identifier = node address 0x2302:001 + 0x580 (cannot be changed)
 
0x1201
SDO2 server parameter
Setting the identifiers for the SDO server channel 2
–
See Lenze image: 0x2304:031
 
–
See Lenze image: 0x2304:032
 
0x1400
RPDO1 communication parameter
Setting the communication parameters for RPDO1
–
See Lenze image: 0x2304:041
 
–
See Lenze image: 0x2304:042
 
–
See Lenze image: 0x2304:045
 
0x1401
RPDO2 communication parameter
Setting the communication parameters for RPDO2
–
See Lenze image: 0x2304:051
 
–
See Lenze image: 0x2304:052
 
–
See Lenze image: 0x2304:055
 
0x1402
RPDO3 communication parameter
Setting the communication parameters for RPDO3
–
See Lenze image: 0x2304:061
 
–
See Lenze image: 0x2304:062
 
–
See Lenze image: 0x2304:065
 
0x1403
RPDO4 communication parameter
Setting the communication parameters for RPDO4
–
See Lenze image: 0x2304:071
 
–
See Lenze image: 0x2304:072
 
–
See Lenze image: 0x2304:075
 
0x1600
RPDO1 mapping parameter
Data mapping for RPDO1 ... RPDO4
–
Description: Data mapping 
 
0x1601
RPDO2 mapping parameter
0x1602
RPDO3 mapping parameter
0x1603
RPDO4 mapping parameter
0x1800
TPDO1 communication parameter
Setting the communication parameters for TPDO1
–
See Lenze image: 0x2304:081
 
–
See Lenze image: 0x2304:082
 
–
See Lenze image: 0x2304:083
 
–
See Lenze image: 0x2304:085
 
0x1801
TPDO1 communication parameter
Setting the communication parameters for TPDO2
–
See Lenze image: 0x2304:091
 
–
See Lenze image: 0x2304:092
 
–
See Lenze image: 0x2304:093
 
–
See Lenze image: 0x2304:095
 
0x1802
TPDO1 communication parameter
Setting the communication parameters for TPDO3
–
See Lenze image: 0x2304:101
 
–
See Lenze image: 0x2304:102
 
–
See Lenze image: 0x2304:103
 
–
See Lenze image: 0x2304:105
 
0x1803
TPDO1 communication parameter
Setting the communication parameters for TPDO4
–
See Lenze image: 0x2304:111
 
–
See Lenze image: 0x2304:112
 
–
See Lenze image: 0x2304:113
 
–
See Lenze image: 0x2304:115
 
0x1A00
TPDO1 mapping parameter
Data mapping for TPDO1 ... TPDO4
–
Description: Data mapping 
 
0x1A01
TPDO2 mapping parameter
0x1A02
TPDO3 mapping parameter
0x1A03
TPDO4 mapping parameter