The responses to CANopen errors such as missing PDOs or heartbeat frames can be configured via the following parameters.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2304:021
CANopen settings: Communication error
Selection of the NMT state to which the inverter is to change automatically if a failure of a CANopen node or an internal error is detected in the "Operational" state.
Image of the CANopen object 0x1029:001
These also include the following communication errors:
–
Change-over of the CAN interface to the "Bus-off" state.
 
–
Occurrence of a "Heartbeat Event".
 
0
Status -> Pre-operational
In the "Pre-operational" state, network management, sync, and emergency telegrams as well as parameter data can be received; process data, however, are ignored.
1
No status change
2
Status -> Stopped
In the "Stopped" state, only network management telegrams can be received.
0x2857:001
CANopen monitoring: RPDO1-Timeout
Selection of the response to triggering the RPDO1 time monitoring.
Associated event ID:
–
822313617 | 0x31038291 - CAN: RPDO1 time-out
 
0
No response
1
Fault > CiA402
2
Warning
0x2857:002
CANopen monitoring: RPDO2-Timeout
Selection of the response to triggering the RPDO2 time monitoring.
Associated event ID:
–
822313618 | 0x31038292 - CAN: RPDO2 time-out
 
0
No response
1
Fault > CiA402
2
Warning
0x2857:003
CANopen monitoring: RPDO3-Timeout
Selection of the response to triggering the RPDO3 time monitoring.
Associated event ID:
–
822313619 | 0x31038293 - CAN: RPDO3 time-out
 
0
No response
1
Fault > CiA402
2
Warning
0x2857:004
CANopen monitoring: RPDO4-Timeout
Associated event ID:
–
822313620 | 0x31038294 - CAN: RPDO4 time-out
 
0
No response
1
Fault > CiA402
2
Warning
0x2857:005
CANopen monitoring: Heartbeat-Timeout Consumer 1
Selection of the response with "Heartbeat Event" in consumer 1.
Associated event ID:
–
822313348 | 0x31038184 - CAN: heartbeat time-out consumer 1
 
0
No response
1
Fault > CiA402
2
Warning
0x2857:006
CANopen monitoring: Heartbeat-Timeout Consumer 2
Selection of the response with "Heartbeat Event" in consumer 2.
Associated event ID:
–
822313349 | 0x31038185 - CAN: heartbeat time-out consumer 2
 
0
No response
1
Fault > CiA402
2
Warning
0x2857:007
CANopen monitoring: Heartbeat-Timeout Consumer 3
Selection of the response with "Heartbeat Event" in consumer 3.
Associated event ID:
–
822313350 | 0x31038186 - CAN: heartbeat time-out consumer 3
 
0
No response
1
Fault > CiA402
2
Warning
0x2857:008
CANopen monitoring: Heartbeat-Timeout Consumer 4
Selection of the response with "Heartbeat Event" in consumer 4.
Associated event ID:
–
822313351 | 0x31038187 - CAN: heartbeat time-out consumer 4
 
0
No response
1
Fault > CiA402
2
Warning
0x2857:010
CANopen monitoring: "Bus-off" state change
Selection of the response to changing to the "Bus off" state.
Associated event ID:
–
822313346 | 0x31038182 - CAN: bus off
 
0
No response
1
Fault > CiA402
2
Warning
0x2857:011
CANopen monitoring: Warning
Selection of the response that is executed in the case of too many incorrectly sent or received CAN telegrams (> 96).
Associated event ID:
–
822313347 | 0x31038183 - CAN: warning
 
0
No response
1
Fault > CiA402
2