Process data transfer

–
The process data serve to control the EtherCAT slaves.
 
–
Process data are, e.g. setpoints, actual values, control words and status words.
 
–
Process input data and process output data are cyclically exchanged between the EtherCAT master and the EtherCAT slaves.
 
–
The transfer is time-critical.
 
–
The process data can be accessed directly by the EtherCAT master. The data is located, for example, in the PLC directly in the I/O area.
 
–
Process data is not saved in the inverter.
 
–
The I/O data mapping defines the EtherCAT objects that are to be transferred cyclically.
 
–
The length of the process data is 0, 4, 8, 12, 16, ... 64 bytes per direction.
 
 
Configuration
The fieldbus network must be selected as the interface for the technology application.
0x4001 = 0 (Fieldbus network)
 
–
Mapping objects:
 
–
Mapping of the available objects is possible in all operating modes as dynamic (free) configuration.
The used EtherCAT objects 0x1630 and 0x1A30 are only accessible via EtherCAT. They are not mapped as Lenze parameters.
 
 
–
The contents can only be selected from the following objects:
 
–
RPDO mapping (0x1630:001 ... 0x1630:016): 0x24E7:001 ... 0x24E7:016
 
–
TPDO mapping (0x1A30:001 ... 0x1A30:016): 0x24E8:001 ... 0x24E8:016
 
 
Pre-assignment:
–
RPDOs: Process input image of the active technology application
 
–
TPDOs: Process output image of the active technology application
 
Number of mapping objects:
–
Standard technology application (1 < 0x4000 < 100)
 
–
8 mapping objects per direction
 
–
PDO length: 32 bytes
 
 
–
User technology application (0x4000 ≥ 10000)
 
–
Max. 16 mapping objects per direction
 
–
PDO length: max. 64 bytes