0x10F1:001
|
Error settings: Local error reaction
|
An error response takes place exclusively via the inverter.
|
|
2
|
Device specific state
|
|
0x10F1:002
|
Error settings: Sync error counter limit
0 ... [20] ... 100
|
Setting for PDO frame failure detection.
When the internal telegram failure error counter reaches the value set here, the inverter changes to the "Safe-Operational" state and causes an error (CiA402 error code 0x8700).
|
|
0x2859:001
|
Network monitoring: Watchdog elapsed
|
Selection of the response to a permanent interruption of the communication to the IO controller.
|
|
0
|
No response
|
|
|
1
|
Fault > CiA402
|
|
2
|
Warning
|
|
0x2859:003
|
Network monitoring: Invalid configuration
|
Selection of the response triggered by the reception of invalid configuration data.
|
|
0
|
No response
|
|
|
1
|
Fault > CiA402
|
|
2
|
Warning
|
|
0x2859:004
|
Network monitoring: Initialisation error
|
Selection of the response triggered by the occurrence of an error during the initialization of the network component.
|
|
0
|
No response
|
|
|
1
|
Fault > CiA402
|
|
2
|
Warning
|
|
0x2859:005
|
Network monitoring: Invalid process data
|
Selection of the response triggered by the reception of invalid process data.
Process data marked as invalid (IOPS is "BAD") are received by the IO Controller. Typically in case of
–
a PLC in STOP state,
–
alarms,
–
acyclic demand data.
|
|
0
|
No response
|
|
|
1
|
Fault > CiA402
|
|
2
|
Warning
|