Resolver error compensation

The actual position detected by the resolver is not exactly the same as the real physical position. There are always more or less substantial deviations.
An identification run of the resolver automatically determines the adjustment values required to compensate for the resolver error.
The determined values have a corrective effect on the cause of occurrence in the following parameters:
Cause
Remedy
Sine and cosine track do not magnetize orthogonally to each other.
Correction of the angle by means of which the two resolver tracks are supplied in a manner relative to one another.
The inductances of the sine and cosine track of the resolver have slightly different values.
Adjusting the gains of the digital-analog converters which feed the resolver tracks.
 
Conditions for executing the identification run
–
Motor
 
–
If possible, execute the identification run before the motor is installed in the machine. Bigger load changes at the motor may have a negative impact on the identification result.
 
–
The motor and resolver must be properly connected to the inverter.
 
–
The motor must rotate freely.
 
 
–
Inverter
 
–
The inverter must be supplied with mains voltage. Check: 0x6041, bit 4 = TRUE.
 
–
The control electronics must be supplied with voltage. For some designs, an external voltage source is required for this purpose.
 
–
The inverter must be connected "online" to the Engineering Tool.
 
 
–
Correct parameterization:
 
–
Number of resolver pole pairs (0x2C43)
 
–
Motor speed-controlled or position-controlled in servo control mode
 
 
 
How to run an identification
1.
Initiate identification run with parameter 0x2822:025.
 
2.
Enable inverter.
The identification run is in standby mode.
 
3.
Approach a constant speed between n = 500 rpm and n = 3000 rpm.
The identification run is started automatically after the drive has reached a constant speed and maintained this speed for the time defined in .
This speed is saved for the identification run. In order that the identification run can be continued again, e.g. after an interruption, the drive must be operated again with this speed.
End of identification run
After the resolver error identification has been executed successfully, the parameters 0x2C44:001 ... 0x2C44:003 are written automatically. The resolver now works with these settings.‌
Brief interruption of the identification run
A short-time interruption, e.g. by removing the controller enable, does not stop the measurement. It is continued after the controller is enabled anew. For the duration of the interruption, the following status message is displayed: "Identification interrupted temporarily".
Cancelling the identification run
The measurement is canceled in case the inverter disable lasts longer or after the timeout time has elapsed. A timeout error is displayed for the identification run, see error messages in the logbook.
 
4.
If the measurement was successful, the motor can be stopped
 
5.
After the process has been completed, save the changed parameters 0x2C44:001 ... 0x2C44:003 in the inverter.‌
 
The »EASY Starter« serves to save the parameter setting of the inverter, see Saving the parameter settings. 
 
Possible responses during the execution
–
Motor running may appear somewhat uneven during identification.
 
–
The direction of rotation can change.
This has no negative impact on the quality of the identification. In this case, the inverter automatically interrupts the identification run and automatically continues it if a constant speed is reached again.
 
–
If the motor already installed in the machine does not have sufficient range in one direction for executing the identification run, you can also reverse the driving direction while the identification is active. In this case, the identification automatically switches to the "Identification temporarily interrupted ". The status is deactivated as soon as a constant speed has been reached again.
 
In the event of an interruption, the identification run is stopped. An error message is displayed.
If 0 % is set, the gain of the respective resolver track is only 95 % of the Lenze setting.
The detected gain can assume values in the range of 0 ... 100 %.‌‌
In case of a successful resolver error compensation, only one of the two gains is adjusted. The other value remains at 100 %.
 
 
Deactivating the resolver error compensation
For deactivating the resolver error compensation, the respective parameters must be reset again to the Lenze setting.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2C54:001
Load encoder/master encoder identification (Resolver): Angle
-100 ... [0] ... 100
Setting of the angle to the resolver error compensation.
0x2C54:002
Load encoder/master encoder identification (Resolver): Cosine track gain
0 ... [100] ... 100 %
Setting of the gain of the cosine track to the resolver error compensation.
0x2C54:003
Load encoder/master encoder identification (Resolver): Sine track gain
0 ... [100] ... 100 %
Setting of the gain of the sine track to the resolver error compensation.
0x2C54:006
Load encoder/master encoder identification (Resolver): Identification status
–
Read only
 
Display of the resolver identification status.
Bit  0
Identification activated
TRUE if:
–
Identification has been started.
 
–
Controller enable is active.
 
FALSE if:
–
Identification has been aborted or completed successfully.
 
–
A timeout error is active.
 
–
The 24V supply has been switched on and default settings are loaded.
 
Bit  2
Identification is running
TRUE if:
–
Identification is running.
 
FALSE if:
–
The motor speed has fallen below the minimum speed of 500 rpm.
 
–
The identification process has been aborted temporarily and is on standby.
 
Bit  3
Identification successful
TRUE if:
–
Identification has been completed successfully.
 
FALSE if:
–
The identification is not completed yet after default settings were loaded.
 
Bit  4
Identification failed
TRUE if:
–
A timeout error has occurred.
 
FALSE if:
–
Identification has been completed successfully.
 
0x2C54:008
Load encoder/master encoder identification (Resolver): Cosine track offset
-100.000 ... [0.000] ... 100.000 %
0x2C54:009
Load encoder/master encoder identification (Resolver): Sine track offset
-100.000 ... [0.000] ... 100.000 %
0x2C54:013
Load encoder/master encoder identification (Resolver): Dead time compensation resolver evaluation
0.0 ... [100.0] ... 500.0 %