Restarting or stopping the communication

The communication needs to be restarted after changes to the interface configuration (e. g. station address and IP configuration) so the changed settings become effective without switching the line voltage.
There are two options for restarting the communication:
–
Set 0x2380 to 1 (restart with current values)
 
–
Set 0x2380 to 2 (restart with the values saved last)
 
The following option can be used to stop communication:
–
Set 0x2380 to 5 (stop network communication)
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2380
PROFINET communication
Restart / stop communication
–
When the device command has been executed successfully, the value 0 is shown.
 
0
No action/no error
Only status feedback
1
Restart with current values
Restart communication with the current values.
2
Restart with stored values
Restart communication with the values of the PROFINET parameters that have been saved last (0x2381:001 ... 0x2381:009).
5
Stop network communication
Stop communication
10
In progress
Only status feedback
11
Action cancelled
12
Fault