Settings in the Siemens »TIA Portal«
Here, commissioning with the Siemens »TIA Portal« is described. Please note that in the standard setting of the Siemens »TIA Portal« changes of network parameters carried out by a Lenze engineering tool (e. g. »EASY Starter«) may be overwritten.
1.
Go to the device configuration and open the "net view" to drag the inverter from the catalog to the net view of the PROFINET.
2.
Assign the inverter to the associated IO-Controller.
3.
Mark the inverter and change to the "device view".
4.
Set the IP address and the station name ("PROFINET device name") in "Properties".
See:
Station name and IP configuration
See:
Station name and IP configurationIn order that the inverter can be identified via Ethernet when the IO controller is switched off, the station name and the IP configuration must be saved in the inverter with mains failure protection via the separate entry with the »EASY Starter«. 0x2022:003
5.
Below the device name and the name of the device description file, the device view shows the pre-assignment of output and input process data words.
In slot 1, pre-assigned process data words can be changed.
When using PROFIsafe, you can add safety process data in slot 2.
PROFIsafe
In slot 1, pre-assigned process data words can be changed.
When using PROFIsafe, you can add safety process data in slot 2.
PROFIsafe 6.
Save the project in the engineering tool.
7.
Load the configuration into the IO-Controller.
8.
Set the IO-Controller to "RUN".