Position recovery after mains switching
The home position can be saved when switching off (power off) in order to be able to do without a reference run after switching on again. The inverter reconstructs the absolute actual position and the home position with high precision based on the new values from the encoder and the values stored at switch-off.
Preconditions
Position reconstruction is only possible with encoders that detect the absolute position at least within one revolution.
–
Suitable encoders:
–
Absolute value encoder - HIPERFACE®-SinCos (single-turn, multi-turn)
–
Absolute value encoder - SSI
–
Absolute value encoder - SSI-SinCos
–
Absolute value encoder - HIPERFACE DSL® (One Cable Technology, OCT)
–
Two-pole resolvers (number of pole pairs = 1)
–
Special SinCos encoder with increment/period number = 1 (the SinCos evaluation enables the display of the absolute position over one revolution)
–
The reference was known before switching off:
0x282A:004, bit 2 = [TRUE]
0x282A:004, bit 2 = [TRUE]–
The function is activated.
–
In the switched-off state, the drive was moved maximally within the permissible limits:
–
Single-turn absolute value encoder and resolver: Max. ±180° = max. ±0.5 rev.
–
Multi-turn absolute value encoder: Max. ±2048 rev. x 360° = max ±737280° = max. ±2048 rev.
The user must ensure that the current position can be recognized unambiguously!
This means that the user must ensure that the drive does not move beyond the maximum values when the power is off. For example, by using a holding brake.
Details
Behavior of the drive:
–
If the angle of rotation is smaller than the maximum value, the absolute actual position is reconstructed in relation to the home position. The drive changes to normal operation without homing.
–
If the angle of rotation is greater than the maximum value, the home position is deleted. A new homing is necessary.
Referencing is always necessary for drives with high-pole resolvers with pole pair number > 1.
Incremental encoders (SinCos, TTL) with a number of increments > 1
Additional monitoring of movement during power off
This monitoring can be used to detect a movement in a narrower tolerance range and process this information in the application. Due to its principle, this monitoring can only evaluate movements within the maximum display range of the absolute value encoder described above.
This monitoring is not required for the position reconstruction itself.
Activate additional monitoring of movement during power off:
–
Activate function.
–
Set the permissible angle of rotation.
–
Single-turn absolute value encoder and resolver: -180° < value < ±180°
–
Multi-turn absolute value encoder: -7372800° < value < +737280°
Parameter