Positioning with an i550

The current count of the i550 position counter (0x2C49:003) can be used for simple position control in the controller.

See also: (This should link to,, “Commissioning devices” – “Inverters” – “i500 frequency inverter” – “i550 cabinet or protex” – “Additional functions” – “Position counter”)

The procedure for using the position counter in the control is described below:

How to connect an additional encoder node for the i550 to the PLC via the EtherCAT system bus in the >>PLC Designer<<:

 

1. Add the encoder node to the i550 node via "add device...".

1. add device

2. select encoder node

  • The encoder will be displayed below the i550 device.

 

2. for a simple position control, the following settings must be made in the i550_Motion_Axis:

 

  • Switching the axis mode (sub 27) from "Simple mode [0]" to "Standard mode [1]".

1. Open the Motion Axis dialogue

Via

2. “Settings”

3. “Overview/Kinematics”

4. Set the “Axis mode” to “Standard mode [1]”

  • Set the motion axis to external position control (subindexes 90 and 92)

1. Open the Motion Axis dialogue

2. “Settings”

3. “Overview\Position controller”

4. “Default control mode” = “Poscontrol ext. encoder [1]”

5. “Ext. encoder” = “i500_Encoder_Axis”

The described procedure is available from the following i550 device description versions:

  • I550 cabinet\protec FW07.00 from Version 7.0.1.7
  • I550 cabinet\protec FW06.04 from Version 6.4.0.2
  • I550 motec FW04.03 from Version 4.3.0.1

 

For older versions of firmware and device description, include parameter 16#2C49:03 in the PDO mapping of the i550 unit.

As an Encoder-Axis-Node a LM_FreeEncoder-Axis must be used and the mapped position must be assigned to the diEncoder position of the LM_FreeEncoder.

(See the chapter here; a link should be provided to the chapter “PLC Designer (3.x) libraries” – “FAST Motion” – “L_MC1P_MotionControlBasic for single axes” – “Motion axes (Axis_Ref)” – “FreeEncoder application example” – “Use of ‘free encoders’”).