Operating modes of the traverser

The working range of the traverser is defined by the end positions. The currently active end positions are saved as persistent data persistentVar : L_TW2P_PersistentVarTraverserBase:

Identifier

Data type

Description

lrModLowerPos

LREAL

Actual lower reversal point

  • Unit: units

  • Initialwert: 0.0

lrModUpperPos

LREAL

Actual upper reversal point

  • Unit: units

  • Initial value: 200.0

The source of the end positions for the traversing area is also determined by selecting the operating mode of the traversing unit.

Identifier

Data type

Description

eOperationMode

L_TW2P_TraverserOperation
Mode

 

 

Operating mode of the traversing drive

0

Position (Initial value):

  • The upper and lower reversal positions are specified as position values.

  • The drive must be referenced so that this operating mode can be used.

1

Switches:

  • Traversing operation between two limit switches.

  • If a travel range limit switch is reached (input xReversingSwitchLower/xReversingSwitchUpper =TRUE), the reversing procedure with delay, edge stop etc. begins.

  • The limit switches must be installed/wired correctly!

2

CoilData:

  • Use of the geometry of the conical coil.

 

Note: The diameter is required for this.