L_IE1P_ResetErrorGlobal
This FB can be used to request a reset of all acknowledgeable errors. The outputxResetActive signals that an error acknowledgement has just been requested somewhere.
Supported devices
|
i950 |
The error reset works globally, i.e. errors in other modules/ components are also reset. |
|
c5x0 |
No limitation |
|
32xxC |
no function . |
|
|
|
|
L_IE1P_ResetErrorGlobal |
|
|
|
|
|---|---|---|---|---|---|---|---|
|
BOOL |
– |
xResetError |
xError |
– |
BOOL |
||
|
eErrorID |
– |
L_IE1P_Error |
|||||
|
xErrorResetActive |
– |
BOOL |
|||||
|
|
|
|
|
|
|
|
|
Inputs
|
Name Datentyp |
Information/possible settings |
|
|---|---|---|
|
xResetError BOOL |
FALSE ä TRUE |
Error reset for all acknowledgeable errors. An error can only be reset if the triggering event is no longer pending, i.e., if input xSetEror is no longer TRUE for errors triggered by the application. |
Outputs
|
Name Datentyp |
Value/meaning |
|
|---|---|---|
|
xError BOOL |
TRUE |
An error has occured. For details see eErrorID . |
|
eErrorID L_IE1P_Error
|
If xError = TRUE: Error number for the error that occurred within the FB. Reference Manual " FAST Technology Modules ": Here you will find information on error or warning messages. |
|
|
xErrorResetActive BOOL |
TRUE |
An global error reset has been executed |
|
xResetActive BOOL |
TRUE |
An acknowledgement of the error (error reset) has been requested by the application or the "PLC Designer" / "EASY Starter". The status signal is independent of whether or not an error has occurred. |