EtherCAT device diagnostics

The diagnostic parameters are parameters of the controller.
The master is unable to access these parameters via the EtherCAT device interface.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2362:007
Active EtherCAT settings: Tx length
–
Read only
 
Display of the length of the transmitted cyclic data in bytes.
A value other than zero is only displayed if the master / slave process data is configured correctly.
0x2362:008
Active EtherCAT settings: Rx length
–
Read only
 
Display of the length of the received cyclic data in bytes.
A value other than zero is only displayed if the master / slave process data is configured correctly.
0x2368
EtherCAT status
–
Read only
 
Display of the current network status.
0
No EtherCAT module
1
Initialization
Network initialization is active.
2
Pre-Operational
The network is active.
3
Bootstrap
Firmware update active.
4
Safe-Operational
–
SDO transmission (CoE communication via mailbox) is possible.
 
–
PDO transmission:
 
–
The input data in the process image are updated.
 
–
The output data from the process image are not transmitted.
 
 
8
Operational
Normal operation
0x2369
EtherCAT error
–
Read only
 
Bit  0
Watchdog elapsed
The SyncManager watchdog has triggered.
Bit  2
Invalid configuration
The configuration sent by the EtherCAT master is invalid.
Bit  3
Stack init error
Internal error when initializing the interface.
Bit  4
Invalid process data
The flag indicates that the process data is invalid.