Process data mapping in master / slave does not match
–
The "EtherCAT device" icon in the »PLC Designer« remains red.
–
The EtherCAT master issues one of the following messages for the slave during the transition to the "Safe-Operational" status:
–
CoE 0x16xx:0 SDO abort 'object cannot be mapped in PDO'.
–
CoE 0x1C1x:0 SDO abort 'object cannot be mapped in PDO'.
–
The 'Process Data Valid' flag in 'Status I/O Mapping' remains set to FALSE.
Remedy
–
Check the mapping in the master and slave.
–
Perform a device scan in the master when the EtherCAT slave is at least in the "Pre-Operational" status.
If modules that were not configured on the EtherCAT master are added to the EtherCAT device, the EtherCAT slave will enter the "Operational" status without data exchange taking place with the EtherCAT master.