0x400C:001
(P593.01)
|
Process output data: AC Drive status word
(Process data OUT: AC status word)
|
Mappable status word with bit assignment in compliance with EtherNet/IP™ AC drive profile.
|
|
Bit 0
|
Fault/Trip active
|
|
|
Bit 1
|
Warning active
|
|
Bit 2
|
Running forward
|
|
Bit 3
|
Running reverse
|
|
Bit 4
|
Ready
|
|
Bit 5
|
Network control active
|
|
Bit 6
|
Network setpoint active
|
|
Bit 7
|
At Reference
|
|
Bit 8
|
Profile-State bit 0
|
The drive status is coded as follows:
0: Manufacturer-specific (reserved)
1: Startup (drive initialisation)
2: Not_Ready (mains voltage switched off)
3: Ready (mains voltage switched on)
4: Enabled (drive has received run command)
5: Stopping (drive has received stop command and is
stopped)
6: Fault_Stop (drive is stopped due to a fault)
7: Faulted (faults have occurred)
|
|
Bit 9
|
Profile-State bit 1
|
|
Bit 10
|
Profile-State bit 2
|
|
Bit 11
|
Profile-State bit 3
|
|
Bit 12
|
Process controller active
|
|
|
Bit 13
|
Torque mode active
|
|
Bit 14
|
Current limit reached
|
|
Bit 15
|
DC braking active
|