Parameter attribute list Data mapping
Data mapping serves to define which process data are transmitted cyclically via the process data channels.
Details
Data mapping (in the case of CANopen also referred to as "PDO mapping") is preconfigured for control of the inverter via the device profile CiA 402:
–
RPDO1 = 0x6040 (CiA control word) and 0x6042 (P781.00) (Set speed).
–
TPDO1 = 0x6041 (P780.00) (CiA status word) and 0x6044 (P783.00) (Actual speed).
Variable PDO mapping
The inverter supports variable PDO mapping for individual drive solutions. With 8 mapping entries each, 8-bit, 16-bit and 32-bit parameters can be assigned to a PDO in any order.
The total length of the mapped parameters must not exceed 8 bytes. The PDO mapping cannot be applied to all parameters. The mappable parameters are marked correspondingly in the parameter attribute list.
Parameter attribute list
Parameter attribute list The process of variable PDO mapping only allows the following procedure:
1.
Set PDO to "invalid": set bit 31 in the corresponding identifier to "1".
Identifiers:
0x1400:001 (P540.01) ... 0x1402:001 (P542.01) or
0x1800:001 (P550.01) ... 0x1802:001 (P552.01)
Identifiers:
0x1400:001 (P540.01) ... 0x1402:001 (P542.01) or
0x1800:001 (P550.01) ... 0x1802:001 (P552.01)
2.
Set PDO mapping to "invalid": set subindex 0 in the mapping parameter to "0".
Mapping parameters:
0x1600:000 ... 0x1602:000 or
0x1A00:000 ... 0x1A02:000
Mapping parameters:
0x1600:000 ... 0x1602:000 or
0x1A00:000 ... 0x1A02:000
3.
Set desired PDO mapping via the corresponding mapping entries.
Format: 0xiiiissll
(iiii = hexadecimal index,
ss = hexadecimal subindex,
ll = hexadecimal data length)
Format: 0xiiiissll
(iiii = hexadecimal index,
ss = hexadecimal subindex,
ll = hexadecimal data length)
4.
Set subindex 0 in the mapping parameter to valid value (number of mapped parameters).
Mapping parameters:
0x1600:000 ... 0x1602:000 or
0x1A00:000 ... 0x1A02:000
Mapping parameters:
0x1600:000 ... 0x1602:000 or
0x1A00:000 ... 0x1A02:000
5.
Set PDO back to "valid": set bit 31 in the corresponding identifier to "0".
Identifiers:
0x1400:001 (P540.01) ... 0x1402:001 (P542.01) or
0x1800:001 (P550.01) ... 0x1802:001 (P552.01)
Identifiers:
0x1400:001 (P540.01) ... 0x1402:001 (P542.01) or
0x1800:001 (P550.01) ... 0x1802:001 (P552.01)
Parameter