Information on the network

The following parameters serve to diagnose the communication activities between the inverter and the Modbus network.
 
The following parameters show information on the network.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2322:001
(P511.01)
Active Modbus settings: Active node ID
(Modbus diag.: Active node ID)
–
Read only
 
Display of the active node address.
0x2322:002
(P511.02)
Active Modbus settings: Active baud rate
(Modbus diag.: Active baud rate)
–
Read only
 
Display of the active baud rate.
0
Automatic
Optionally setting of the baud rate (instead of setting via DIP switch b).
–
The baud rate set here is only effective if DIP switch b was set to ON before mains switching. Otherwise automatic baud rate detection is active.
 
–
A change in the baud rate only becomes effective after a restart of Modbus communication.
 
–
If the automatic baud rate detection function is activated, the first 5 ... 10 messages are lost after switch-on.
 
1
2400 bps
2
4800 bps
3
9600 bps
4
19200 bps
5
38400 bps
6
57600 bps
7
115200 bps
0x2322:003
(P511.03)
Active Modbus settings: Data format
(Modbus diag.: Data format)
–
Read only
 
Display of the active data format.
0
Automatic
Automatic data format detection.
–
With this setting, the first 5 ... 10 messages are lost after switch-on.
 
1
8, E, 1
8 data bits, even parity, 1 stop bit
2
8, O, 1
8 data bits, odd parity, 1 stop bit
3
8, N, 2
8 data bits, no parity bit, 2 stop bits
4
8, N, 1
8 data bits, no parity bit, 1 stop bit
0x2323
(P509.00)
Modbus switch position
(Modbus switch)
–
Read only
 
Display of the DIP switch setting at the last mains power-on.
–
The value displayed corresponds to the sum of all DIP switch values (except for DIP switches for terminating resistor).
 
0x232A:001
(P580.01)
Modbus statistics: Messages received
(Modbus statistic: Mess. received)
–
Read only
 
Display of the total number of messages received.
–
This counter counts both valid and invalid messages.
 
–
After the maximum value has been reached, the counter starts again "0".
 
0x232A:002
(P580.02)
Modbus statistics: Valid messages received
(Modbus statistic: Val. mess. rec.)
–
Read only
 
Display of the number of valid messages received.
–
After the maximum value has been reached, the counter starts again "0".
 
0x232A:003
(P580.03)
Modbus statistics: Messages with exceptions
(Modbus statistic: Mess. w. exc.)
–
Read only
 
Display of the number of messages with exceptions that have been received.
–
After the maximum value has been reached, the counter starts again "0".
 
0x232A:004
(P580.04)
Modbus statistics: Messages with errors
(Modbus statistic: Mess. w. errors)
–
Read only
 
Display of the number of messages received with a faulty data integrity (parity, CRC).
–
After the maximum value has been reached, the counter starts again "0".
 
0x232A:005
(P580.05)
Modbus statistics: Messages sent
(Modbus statistic: Messages sent)
–
Read only
 
Display of the total number of messages sent.
–
After the maximum value has been reached, the counter starts again "0".
 
0x232E:001
(P583.01)
Modbus diagnostics of last Rx data: Offset
(Rx data diagn.: Rx data offset)
0 ... [0] ... 240
For purposes of diagnostics, the last message received (max. 16 bytes) is shown in 0x232E:002 (P583.02)...0x232E:017 (P583.17). For longer messages, an offset can be specified here, indicating from which byte of the message the display of the 16 bytes is to start.
0x232E:002
(P583.02)
Modbus diagnostics of last Rx data: Data byte 0
(Rx data diagn.: Last RxD byte0)
–
Read only
 
Display of the message received last.
0x232E:003
(P583.03)
Modbus diagnostics of last Rx data: Data byte 1
(Rx data diagn.: Last RxD byte1)
–
Read only
 
0x232E:004
(P583.04)
Modbus diagnostics of last Rx data: Data byte 2
(Rx data diagn.: Last RxD byte2)
–
Read only
 
0x232E:005
(P583.05)
Modbus diagnostics of last Rx data: Data byte 3
(Rx data diagn.: Last RxD byte3)
–
Read only
 
0x232E:006
(P583.06)
Modbus diagnostics of last Rx data: Data byte 4
(Rx data diagn.: Last RxD byte4)
–
Read only
 
0x232E:007
(P583.07)
Modbus diagnostics of last Rx data: Data byte 5
(Rx data diagn.: Letzt RxD-Byte5)
–
Read only
 
0x232E:008
(P583.08)
Modbus diagnostics of last Rx data: Data byte 6
(Rx data diagn.: Last RxD byte6)
–
Read only
 
0x232E:009
(P583.09)
Modbus diagnostics of last Rx data: Data byte 7
(Rx data diagn.: Last RxD byte7)
–
Read only
 
0x232E:010
(P583.10)
Modbus diagnostics of last Rx data: Data byte 8
(Rx data diagn.: Last RxD byte8)
–
Read only
 
0x232E:011
(P583.11)
Modbus diagnostics of last Rx data: Data byte 9
(Rx data diagn.: Last RxD byte9)
–
Read only
 
0x232E:012
(P583.12)
Modbus diagnostics of last Rx data: Data byte 10
(Rx data diagn.: Last RxD byte10)
–
Read only
 
0x232E:013
(P583.13)
Modbus diagnostics of last Rx data: Data byte 11
(Rx data diagn.: Last RxD byte11)
–
Read only
 
0x232E:014
(P583.14)
Modbus diagnostics of last Rx data: Data byte 12
(Rx data diagn.: Last RxD byte12)
–
Read only
 
0x232E:015
(P583.15)
Modbus diagnostics of last Rx data: Data byte 13
(Rx data diagn.: Last RxD byte13)
–
Read only
 
0x232E:016
(P583.16)
Modbus diagnostics of last Rx data: Data byte 14
(Rx data diagn.: Last RxD byte14)
–
Read only
 
0x232E:017
(P583.17)
Modbus diagnostics of last Rx data: Data byte 15
(Rx data diagn.: Last RxD byte15)
–
Read only
 
0x232F:001
(P585.01)
Modbus diagnostics of last Tx data: Offset
(Tx data diagn.: Tx data offset)
0 ... [0] ... 240
For purposes of diagnostics, the last message sent (max. 16 bytes) is shown in 0x232F:002 (P585.02)...0x232F:017 (P585.17). For longer messages, an offset can be specified here, indicating from which byte of the message the display of the 16 bytes is to start.
0x232F:002
(P585.02)
Modbus diagnostics of last Tx data: Data byte 0
(Tx data diagn.: Last TxD byte0)
–
Read only
 
Display of the message sent last.
0x232F:003
(P585.03)
Modbus diagnostics of last Tx data: Data byte 1
(Tx data diagn.: Last TxD Byte1)
–
Read only
 
0x232F:004
(P585.04)
Modbus diagnostics of last Tx data: Data byte 2
(Tx data diagn.: Last TxD byte2)
–
Read only
 
0x232F:005
(P585.05)
Modbus diagnostics of last Tx data: Data byte 3
(Tx data diagn.: Last TxD byte3)
–
Read only
 
0x232F:006
(P585.06)
Modbus diagnostics of last Tx data: Data byte 4
(Tx data diagn.: Last TxD byte4)
–
Read only
 
0x232F:007
(P585.07)
Modbus diagnostics of last Tx data: Data byte 5
(Tx data diagn.: Last TxD byte5)
–
Read only
 
0x232F:008
(P585.08)
Modbus diagnostics of last Tx data: Data byte 6
(Tx data diagn.: Last TxD byte6)
–
Read only
 
0x232F:009
(P585.09)
Modbus diagnostics of last Tx data: Data byte 7
(Tx data diagn.: Last TxD byte7)
–
Read only
 
0x232F:010
(P585.10)
Modbus diagnostics of last Tx data: Data byte 8
(Tx data diagn.: Last TxD byte8)
–
Read only
 
0x232F:011
(P585.11)
Modbus diagnostics of last Tx data: Data byte 9
(Tx data diagn.: Last TxD byte9)
–
Read only
 
0x232F:012
(P585.12)
Modbus diagnostics of last Tx data: Data byte 10
(Tx data diagn.: Last TxD byte10)
–
Read only
 
0x232F:013
(P585.13)
Modbus diagnostics of last Tx data: Data byte 11
(Tx data diagn.: Last TxD byte11)
–
Read only
 
0x232F:014
(P585.14)
Modbus diagnostics of last Tx data: Data byte 12
(Tx data diagn.: Last TxD byte12)
–
Read only
 
0x232F:015
(P585.15)
Modbus diagnostics of last Tx data: Data byte 13
(Tx data diagn.: Last TxD byte13)
–
Read only
 
0x232F:016
(P585.16)
Modbus diagnostics of last Tx data: Data byte 14
(Tx data diagn.: Last TxD byte14)
–
Read only
 
0x232F:017
(P585.17)
Modbus diagnostics of last Tx data: Data byte 15
(Tx data diagn.: Last TxD byte15)
–
Read only