Information on the network
The following parameters serve to diagnose the communication activities between the inverter and the Modbus network.
The following parameters show information on the network.
Parameter
|
Address
|
Name / setting range / [default setting]
|
Information
|
|
|
0x23B2:001
(P511.01)
|
Active Modbus TCP settings: Active IP address
(Act. MBTCP sett.: Act. IP address)
–
Read only
–
From version 04.00
|
Display of the active IP address.
|
|
|
0x23B2:002
(P511.02)
|
Active Modbus TCP settings: Active subnet
(Act. MBTCP sett.: Act. subnet)
–
Read only
–
From version 04.00
|
Display of the active subnet mask.
|
|
|
0x23B2:003
(P511.03)
|
Active Modbus TCP settings: Active gateway
(Act. MBTCP sett.: Act. gateway)
–
Read only
–
From version 04.00
|
Display of the active gateway address.
Example
The setting 276344004 corresponds to the gateway address 196.172.120.16.
–
276344004 = 0x1078ACC4
à 0xC4.0xAC.0x78.0x10 = 196.172.120.16 |
|
|
0x23B2:005
(P511.05)
|
Active Modbus TCP settings: MAC address
(Act. MBTCP sett.: MAC address)
–
Read only
–
From version 04.00
|
Display of the active MAC address.
|
|
|
0x23B3
(P509.00)
|
Switch position
(Switch position)
–
Read only
–
From version 04.00
|
Display of the rotary encoder switch setting at the last mains power-on.
|
|
|
0x23B5:001
(P513.01)
|
Active port settings: Port 1
(Act. port sett.: Port 1)
–
Read only
–
From version 04.00
|
Display of the baud rate set for Port 1 in 0x23B4:001 (P512.01).
|
|
|
0
|
Not connected
|
||
|
1
|
10 Mbps/Half Duplex
|
||
|
2
|
10 Mbps/Full Duplex
|
||
|
3
|
100 Mbps/Half Duplex
|
||
|
4
|
100 Mbps/Full Duplex
|
||
|
0x23B5:002
(P513.02)
|
Active port settings: Port 2
(Act. port sett.: Port 2)
–
Read only
–
From version 04.00
|
Display of the baud rate set for Port 2 in 0x23B4:001 (P512.01).
|
|
|
0
|
Not connected
|
||
|
1
|
10 Mbps/Half Duplex
|
||
|
2
|
10 Mbps/Full Duplex
|
||
|
3
|
100 Mbps/Half Duplex
|
||
|
4
|
100 Mbps/Full Duplex
|
||
|
0x23B8
(P516.00)
|
Modbus TCP module status
(MBTCP modul. stat)
–
Read only
–
From version 04.00
|
Display of the TCP module state.
|
|
|
0
|
Power off
|
||
|
1
|
Initialization
|
||
|
2
|
Warning
|
||
|
3
|
Fault
|
||
|
4
|
No configuration
|
||
|
5
|
Operational
|
||
|
0x23B9
(P517.00)
|
Modbus TCP/IP network status
(MBTCP netw stat)
–
Read only
–
From version 04.00
|
Display of the active network status.
|
|
|
0
|
No configuration
|
||
|
1
|
Initialization
|
||
|
2
|
Connection time-out
|
||
|
3
|
Configuration error
|
||
|
4
|
Not connected
|
||
|
5
|
Connection established
|
||
|
0x23BA:001
(P580.01)
|
Modbus TCP statistics: Messages received
(MBTCP statistics: Rx messages)
–
Read only
–
From version 04.00
|
Display of the total number of messages received.
–
This counter counts both valid and invalid messages.
–
After the maximum value has been reached, the counter starts again "0".
|
|
|
0x23BA:002
(P580.02)
|
Modbus TCP statistics: Valid messages received
(MBTCP statistics: Valid Rx messag.)
–
Read only
–
From version 04.00
|
Display of the number of valid messages received.
–
After the maximum value has been reached, the counter starts again "0".
|
|
|
0x23BA:003
(P580.03)
|
Modbus TCP statistics: Messages with exceptions
(MBTCP statistics: Mess. w. except)
–
Read only
–
From version 04.00
|
Display of the number of messages with exceptions that have been received.
–
After the maximum value has been reached, the counter starts again "0".
|
|
|
0x23BA:005
(P580.05)
|
Modbus TCP statistics: Messages sent
(MBTCP statistics: Tx messages)
–
Read only
–
From version 04.00
|
Display of the total number of messages sent.
–
After the maximum value has been reached, the counter starts again "0".
|
|
|
0x23BE:001
(P585.01)
|
Modbus TCP/IP diagnostics of last Rx/Tx data: Receive offset
(MBTCP Tx/Rx diag: Rx offset)
0 ... [0] ... 240
–
From version 04.00
|
For diagnostic purposes, the last received message (max. 16 bytes) is displayed in 0x23BE:002 (P585.02). For longer messages, an offset can be specified here, indicating from which byte of the message the display of the 16 bytes is to start.
|
|
|
0x23BE:002
(P585.02)
|
Modbus TCP/IP diagnostics of last Rx/Tx data: Last Rx message
(MBTCP Tx/Rx diag: Last Rx message)
–
Read only
–
From version 04.00
|
Display of the message received last.
|
|
|
0x23BE:003
(P585.03)
|
Modbus TCP/IP diagnostics of last Rx/Tx data: Transmit offset
(MBTCP Tx/Rx diag: Tx offset)
0 ... [0] ... 240
–
From version 04.00
|
For diagnostic purposes, the last sent message (max. 16 bytes) is displayed in 0x23BE:004 (P585.04). For longer messages, an offset can be specified here, indicating from which byte of the message the display of the 16 bytes is to start.
|
|
|
0x23BE:004
(P585.04)
|
Modbus TCP/IP diagnostics of last Rx/Tx data: Last Tx message
(MBTCP Tx/Rx diag: Last Tx message)
–
Read only
–
From version 04.00
|
Display of the message sent last.
|
|