Trouble

This device state becomes active if a serious system fault occurs. This means that the inverter is no longer able to drive the motor in a controlled way. The inverter is switched off immediately.
–
The pulse inhibit is active (pulses of the inverter are inhibited).
 
–
The motor is torqueless.
 
–
The motor brake, if available, is closed.
 
–
Operation is inhibited.
 
–
The inverter can be parameterised.
 
 
1
From all states
2
Power section inhibited (pulse inhibit)
3
Power section enabled
 
Bit pattern in the CiA status word (0x6041 (P780.00))
Bit 15 ... 8
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
Reserved
(specific)
Warning active
Operation inhibited
Quick stop active
DC bus ready for operation
Fault active
Operation enabled
Switched on
Ready to switch on
X = state is not relevant
X
X
0
X
X
1
0
0
0
 
This device state can only be left with the "Reset fault" command if the cause of the fault has been removed.