Function codes
The inverter supports the following function codes:
|
Function code
|
Function name
|
Info
|
|
|
3
|
0x03
|
Read Holding Registers
|
Reading of a single register or a group of several interconnected registers.
|
|
6
|
0x06
|
Preset Single Register
|
Writing of a single register.
|
|
16
|
0x10
|
Preset Multiple Registers
|
Writing of a single register or a group of several interconnected registers.
|
|
23
|
0x17
|
Read/Write 4X Registers
|
Reading and writing within a transaction:
–
Writing of a data block into a group of several interconnected registers.
–
Reading from a block of interconnected registers.
|
Frame structure
|
Modbus Application Header (MBAP)
|
Protocol Data Unit (PDU)
|
|||||
|
Transaction number
|
Protocol characters
(always 0x0000)
|
Number of the bytes still to follow
|
Unit identifier
|
Function code
|
Data / error code
|
|
|
2 bytes
|
2 bytes
|
2 bytes
|
1 byte
|
1 byte
|
n byte
|
|
Tab. 1: ADU (Application Data Unit)
Communication is established on the basis of the client/server mode. Communication is always started by a client request.
The server (inverter) then either gives a valid response or outputs an error code (provided that the request has been received and evaluated as valid message).
In case of a valid answer, the function code is returned. In the event of an error, a function code assigned to the request is returned.
Error causes can be invalid CRC checksums, non-supported function codes or impermissible data accesses.
Elements of the ADU:
–
MBAP (7 bytes)
–
Number of the bytes still to follow in the message.
–
Address of the inverter.
–
The other bytes of the header are not described here.
–
Function code
–
The function codes exclusively refer to "4X registers", i. e. registers from the address 4000.
–
All data in the inverter can only be accessed via these 4X registers, see: Data mapping
–
The 4xxxx reference is implicit, i. e. given by the function code used. In the frame therefore the leading 4 is omitted in the addressing process.
–
Lenze supports the basic 1 addressing of Modbus, i.e. the numbering of the registers starts with 1 whereas addressing starts with 0. For example, the address 0 is used in the frame when register 40001 is read.
–
Data or error code
–
Checksum
All ADU contents are represented in the Big Endian format (most significant byte first).
Error codes
In the event of an error, the server (inverter) responds with a function code associated with the message:
|
Function code
|
Associated function code in the event of an error
|
Supported error codes
|
|
0x03
|
0x83
|
0x01, 0x02, 0x03, 0x04
|
|
0x06
|
0x86
|
0x01, 0x02, 0x03, 0x04
|
|
0x10
|
0x90
|
0x01, 0x02, 0x03, 0x04
|
|
0x17
|
0x97
|
0x01, 0x02, 0x03, 0x04
|
|
Error code
|
Designation
|
Cause(s)
|
|
0x01
|
Invalid function code
|
The function code is not supported by the inverter, or the inverter is in a state in which the request is not permissible or in which it cannot be processed.
|
|
0x02
|
Invalid data address
|
The combination of a start address and the length of the data to be transmitted is invalid.
Example: If you have a server with 100 registers, the first register has the address 0 and the last register has the address 99. If there is a request of four registers now, from the start address 96, the request can be processed successfully (for registers 96, 97, 98, and 99). If, however, five registers from the start address 96 are queried, this error code is returned, since the server has no register with the address 100.
|
|
0x03
|
Invalid data value
|
Error in the reset structure of a complex request, e. g. because the data length that has resulted implicitly is not correct.
The cause, however, is not that a (parameter) value is written outside the valid setting range. As a matter of principle, the Modbus protocol has no information on valid setting ranges of single registers or their meaning.
|
|
0x04
|
Server device failure
|
A non-correctable error has occurred while the request was processed in the inverter.
|
Data transfer with function code 3
|
Request
|
|
|
Function code
|
0x03
|
|
Start address
|
0x0000 ... 0xFFFF
|
|
Number of registers (n)
|
0x01 ... 0x7D (1 ... 125)
|
|
Response
|
|
|
Function code
|
0x03
|
|
Number of bytes
|
2 x (number of registers)
|
|
Register value
|
Data in (n) register of 2 bytes each
|
|
Error message
|
|
|
Function code in the event of an error
|
0x83
|
|
Error code
|
01 ... 04
|
Example for data transfer with function code 3
The data from the registers 40108 to 40110 are to be read.
|
Request
|
Info
|
|
|
Function code
|
0x03
|
Function code 3
|
|
Start address (High)
|
0x00
|
Start address 107 (0x006B)
|
|
Start address (Low)
|
0x6B
|
|
|
Number of registers (High)
|
0x00
|
Number of registers = 3 (0x0003)
|
|
Number of registers (Low)
|
0x03
|
|
|
Response
|
Info
|
|
|
Function code
|
0x03
|
Function code 3
|
|
Number of bytes
|
0x06
|
6 bytes are read.
|
|
Value in registers 40108 (High)
|
0x02
|
Data in register 40108: 0x022B (555).
|
|
Value in registers 40108 (Low)
|
0x2B
|
|
|
Value in registers 40109 (High)
|
0x00
|
Data in register 40109: 0x0000 (0).
|
|
Value in registers 40109 (Low)
|
0x00
|
|
|
Value in registers 40110 (High)
|
0x00
|
Data in register 40110: 0x0064 (100).
|
|
Value in registers 40110 (Low)
|
0x64
|
|
Data transfer with function code 6
|
Request
|
|
|
Function code
|
0x06
|
|
Register address
|
0x0000 ... 0xFFFF
|
|
Register value
|
0x0000 ... 0xFFFF
|
|
Response
|
|
|
Function code
|
0x06
|
|
Register address
|
0x0000 ... 0xFFFF
|
|
Register value
|
0x0000 ... 0xFFFF
|
|
Error message
|
|
|
Function code in the event of an error
|
0x86
|
|
Error code
|
01 ... 04
|
Example for data transfer with function code 6
The value "3" (0x0003) is to be written into the register 40002.
|
Request
|
Info
|
|
|
Function code
|
0x06
|
Function code 6
|
|
Register address (High)
|
0x00
|
Register address for register 40002: 1 (0x0001)
|
|
Register address (Low)
|
0x01
|
|
|
Register value (High)
|
0x00
|
Value to be written into the register: 3 (0x0003)
|
|
Register value (Low)
|
0x03
|
|
|
Response
|
Info
|
|
|
Function code
|
0x06
|
Function code 6
|
|
Register address (High)
|
0x00
|
Register address: 1 (0x0001)
|
|
Register address (Low)
|
0x01
|
|
|
Register value (High)
|
0x00
|
Register value: 3 (0x0003)
|
|
Register value (Low)
|
0x03
|
|
Data transfer with function code 16
|
Request
|
|
|
Function code
|
0x10
|
|
Start address
|
0x0000 ... 0xFFFF
|
|
Number of registers (n)
|
0x0001 ... 0x7D (0d125)
|
|
Number of bytes
|
2 x (number of registers)
|
|
Register values
|
Data in (n) register of 2 bytes each
|
|
Response
|
|
|
Function code
|
0x10
|
|
Number of bytes
|
2 x (number of registers)
|
|
Register values
|
Data in (n) register of 2 bytes each
|
|
Error message
|
|
|
Function code in the event of an error
|
0x90
|
|
Error code
|
01 ... 04
|
Example for data transfer with function code 16
In a transaction, the value "10" is to be written into the register 40002 and the value "258" is to be written into the adjacent register 40003.
|
Request
|
|
Info
|
|
Function code
|
0x10
|
Function code 16
|
|
Start address (High)
|
0x00
|
Start address is the register 40002: 1 (0x0001)
|
|
Start address (Low)
|
0x01
|
|
|
Number of registers (High)
|
0x00
|
Number of registers: 2 (0x0002)
|
|
Number of registers (Low)
|
0x02
|
|
|
Number of bytes
|
0x04
|
4 bytes (0x0004) are to be written.
|
|
Register value (High)
|
0x00
|
The value "10" (0x000A) is written into the register with the start address 1 (= register 40002).
|
|
Register value (Low)
|
0x0A
|
|
|
Register value (High)
|
0x01
|
The value "258" (0x0102) is written into the following register (= register 40003).
|
|
Register value (Low)
|
0x02
|
|
Response
|
Info
|
|
|
Function code
|
0x10
|
Function code 16
|
|
Start address (High)
|
0x00
|
Start address: 1 (0x0001)
|
|
Start address (Low)
|
0x01
|
|
|
Number of registers (High)
|
0x00
|
Number of registers: 2 (0x0002)
|
|
Number of registers (Low)
|
0x02
|
|
Data transfer with function code 23
|
Request
|
|
|
Function code
|
0x17
|
|
Start address for reading (High)
|
0x0000 ... 0xFFFF
|
|
Start address for reading (Low)
|
0x0000 ... 0xFFFF
|
|
Number of registers for reading (High)
|
0x00 ... 0xFF
|
|
Number of registers for reading (Low)
|
0x00 ... 0xFF
|
|
Start address for writing (High)
|
0x0000 ... 0xFFFF
|
|
Start address for writing (Low)
|
0x0000 ... 0xFFFF
|
|
Number of registers for writing (High)
|
0x00 ... 0xFF
|
|
Number of registers for writing (Low)
|
0x00 ... 0xFF
|
|
Number of bytes for writing
|
2 x (number of registers)
|
|
Written value 1 (High)
|
0x00 ... 0xFF
|
|
Written value 1 (Low)
|
0x00 ... 0xFF
|
|
....
|
...
|
|
Written value n (High)
|
0x00 ... 0xFF
|
|
Written value n (Low)
|
0x00 ... 0xFF
|
|
Response
|
|
|
Function code
|
0x17
|
|
Number of bytes for reading
|
2 x (number of registers)
|
|
Read value 1 (High)
|
0x00 ... 0xFF
|
|
Read value 1 (Low)
|
0x00 ... 0xFF
|
|
...
|
...
|
|
Read value x (High)
|
0x00 ... 0xFF
|
|
Read value x (Low)
|
0x00 ... 0xFF
|
|
Error message
|
|
|
Function code in the event of an error
|
0x97
|
|
Error code
|
02 ... 04
|
Example for data transfer with function code 23
The following tasks are to be executed with a transaction:
–
The values from six connected registers, starting with register 40005, are to be read.
–
The value "255" is to be written into each of three connected registers, starting with register 40016.
|
Request
|
Info
|
|
|
Function code
|
0x17
|
Function code 23
|
|
Start address for reading (High)
|
0x00
|
Start address for reading is the register 40005: 4 (0x0004)
|
|
Start address for reading (Low)
|
0x04
|
|
|
Number of registers for reading (High)
|
0x00
|
Number of registers for reading: 6 (0x0006))
|
|
Number of registers for reading (Low)
|
0x06
|
|
|
Start address for writing (High)
|
0x00
|
Start address for writing is the register 40016: 15 (0x000F)
|
|
Start address for writing (Low)
|
0x0F
|
|
|
Number of registers for writing (High)
|
0x00
|
Number of registers for writing: 3 (0x0003)
|
|
Number of registers for writing (Low)
|
0x03
|
|
|
Number of bytes for writing
|
0x06
|
6 bytes (0x06) must be provided in 3 registers.
|
|
Written value 1 (High)
|
0x00
|
Data: 255 (0x00FF)
|
|
Written value 1 (Low)
|
0xFF
|
|
|
Written value 2 (High)
|
0x00
|
Data: 255 (0x00FF)
|
|
Written value 2 (Low)
|
0xFF
|
|
|
Written value 3 (High)
|
0x00
|
Data: 255 (0x00FF)
|
|
Written value 3 (Low)
|
0xFF
|
|
|
Response
|
Info
|
|
|
Function code
|
0x17
|
Function code 23
|
|
Number of bytes for reading
|
0x0C
|
12 bytes (0x0C) from 6 registers are read.
|
|
Read value 1 (High)
|
0x00
|
1. written value
Data: 254 (0x00FE)
|
|
Read value 1 (Low)
|
0xFE
|
|
|
Written value 2 (High)
|
0x0A
|
2. written value
Data: 2765 (0x0ACD)
|
|
Read value 2 (Low)
|
0xCD
|
|
|
Read value 3 (High)
|
0x00
|
3. read value
Data: 1 (0x0001)
|
|
Read value 3 (Low)
|
0x01
|
|
|
Read value 4 (High)
|
0x00
|
4. read value
Data: 3 (0x0003)
|
|
Read value 4 (Low)
|
0x03
|
|
|
Read value 5 (High)
|
0x00
|
5. read value
Data: 13 (0x000D)
|
|
Read value 5 (Low)
|
0x0D
|
|
|
Read value 6 (High)
|
0x00
|
6. read value
Data: 255 (0x00FF)
|
|
Read value 6 (Low)
|
0xFF
|
|