ASM field weakening controller (extended)

For a quick commissioning, the calculations and settings are made automatically during the motor calibration.
 
Preconditions
The field weakening controller is only effective in the following motor control types:
–
Servo control (SC ASM)
 
–
Sensorless vector control (SLVC)
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x29E2
DC-bus filter time
1.0 ... [25.0] ... 1000.0 ms
Filter time for the current DC-bus voltage used for field weakening.
0x29E3
Motor voltage filter time
1.0 ... [25.0] ... 1000.0 ms
Filter time for the current motor voltage used for field weakening.
0x29E4
Voltage reserve range
0 ... [5] ... 20 %
Voltage reserve at the transition point to the field weakening, with reference to the current value of the DC-bus voltage.
–
100% = DC-bus voltage 0x2D87