Current controller

For a quick commissioning, the calculations and settings are made automatically during the motor calibration.
 
For typical applications, a manual adaptation of the parameters of the current controller is not recommended. A wrong setting may have a negative effect on the control. For special applications, contact the manufacturer before adapting the parameters.
 
 
Preconditions
The current controller parameters are calculated based on the stator resistance and leakage inductance. Thus, the following parameters must be set correctly, either via optimization or manually (according to manufacturer-data/motor data sheet):
–
0x2C01:002: Stator resistance
 
–
0x2C01:003: Stator leakage inductance
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2942:001
Current controller parameters: Gain
0.00 ... [0.00] ... 750.00 V/A
Gain factor Vp of the current controller.
0x2942:002
Current controller parameters: Reset time
0.01 ... [0.00] ... 2000.00 ms
Reset time Tn of the current controller.