General optimizations

Parameter
Address
Name / setting range / [default setting]
Information
0x2DE0:010
Service settings: Motor control behavior
0 ... [8] ... 65535
–
Setting can only be changed if the inverter is disabled.
 
Optimization of the behavior of the motor control.
Bit 0
Slip compensation via equivalent circuit diagram
Bit 0 = 0: calculation via motor data label (standard).
Bit 0 = 1: calculation of magnetising current based on equivalent circuit diagram (response <= SW 05.02.00).
Bit 1
Imax controller without clamp detection
Bit x = 1: Activation of the respective option.
Bit 2
Motor reference temperatur 20 degree celsius
Bit 3
Enhanced SLVC stop behavior
Bit 4
Earth fault detection disabled
0x2DE0:029
Service settings: Limitation of output voltage
0
Default setting
This setting ensures that the motor is optimally energised and corresponds to the "Minimum" setting for the following motor control modes (0x2C00):
–
SC-ASM
 
–
SLVC
 
–
VFC open loop
 
–
VFC closed loop
 
–
SLSM-PSM
 
1
Minimum
2
Average
This setting increases the motor output voltage, which may be more important in certain applications than optimising the energization of the motor.