General optimizations
Parameter
|
Address
|
Name / setting range / [default setting]
|
Information
|
|
|
0x2DE0:010
|
Service settings: Motor control behavior
0 ... [8] ... 65535
–
Setting can only be changed if the inverter is disabled.
|
Optimization of the behavior of the motor control.
|
|
|
Bit 0
|
Slip compensation via equivalent circuit diagram
|
Bit 0 = 0: calculation via motor data label (standard).
Bit 0 = 1: calculation of magnetising current based on equivalent circuit diagram (response <= SW 05.02.00).
|
|
|
Bit 1
|
Imax controller without clamp detection
|
Bit x = 1: Activation of the respective option.
|
|
|
Bit 2
|
Motor reference temperatur 20 degree celsius
|
||
|
Bit 3
|
Enhanced SLVC stop behavior
|
||
|
Bit 4
|
Earth fault detection disabled
|
||
|
0x2DE0:029
|
Service settings: Limitation of output voltage
|
||
|
0
|
Default setting
|
This setting ensures that the motor is optimally energised and corresponds to the "Minimum" setting for the following motor control modes (0x2C00):
–
SC-ASM
–
SLVC
–
VFC open loop
–
VFC closed loop
–
SLSM-PSM
|
|
|
1
|
Minimum
|
||
|
2
|
Average
|
This setting increases the motor output voltage, which may be more important in certain applications than optimising the energization of the motor.
|
|