Optimising the stalling behaviour

The stalling protection function or the maximum permissible motor current in the field weakening range can be adapted.
–
If the motor stalls in the field weakening range, the override point can be shifted by reducing the set value so that the motor stalling can be prevented.
 
–
If the motor does not provide enough torque in the field weakening range, the set value must be increased.
 
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2B0C
Override field weakening
-500.0 ... [0.0] ... 500.0 Hz
Offset of the override point for field weakening.