Define V/f characteristic shape

For adaptation purposes to different load profiles, you can select the shape of the characteristic:
 
Parameter
Address
Name / setting range / [default setting]
Information
0x2B00
V/f characteristic shape
–
Setting can only be changed if the inverter is disabled.
 
Selection of the V/f characteristic shape for the adaptation to different load profiles.
0
Linear
Linear characteristic for drives with constant load torque over the speed.
1
Quadratic
Square-law characteristic for drives with a square-law load torque over the speed.
–
Square-law V/f characteristics are preferably used for centrifugal pumps and fan drives.
 
–
Please always check whether the corresponding application is suitable for operation with a square-law V/f characteristic!
 
–
If your pump drive or fan drive is not suitable for operation with a square-law V/f characteristic, use the linear V/f characteristic instead.
 
2
Adaptive
User-definable characteristic with 3 grid points.
3
Eco
Linear characteristic with energy optimisation in the partial load operational range.