Configuring the "CiA 402 advanced" TA

The “CiA 402 Advanced” technology application can be used for the following application ranges:
–
Storage and retrieval units
 
–
Robotics
 
–
Applications that require a CiA 402 device with additional motion functions or decentralized data storage
 
 
The “CiA 402 Advanced” technology application serves to extend the standard CiA 402 functions of the inverter.
Kinematics and motion profile are calculated on a higher-level controller. In the controller, the functions of the Lenze L_MC1P library or the L_TT1P library are used. The inverters with the “CiA 402 Advanced” technology application are thus implemented as motion nodes below a controller. The other technology applications are implemented as logic nodes below a controller.
Fig. 1: Interface in the technology application to the safety option
 
Signal propagation delays
The figure shows how the EtherCat slave stack leads the control data and status data through the technology application before they become effective in the motor control. In contrast to the standard CiA 402 operation, this results in a cycle time delay of 1 ms.
 
Data storage
The parameter set is saved on the SD card of the inverter with the “CiA 402 Advanced” technology application. There is no automatic download via the controller to permanently save parameters such as motor data in the inverter.
 
Functional overview
The following extensions for the standard “CiA 402” functionality are implemented in the “CiA 402 Advanced” technology application:
–
Homing according to CiA 402: Homing 
 
–
Position control for application encoder slot B: Position control 
 
–
Quick stop of the application: Quick stop 
 
–
Interface in the technology application to the fieldbus
 
All other functions of the inverter can also be used when the technology application is active. Moreover, with this technology application the inverter can be used as CiA 402 device with PROFIsafe. With the default settings, the inverter acts the same as in the standard CiA 402 operation.
 
Relevant parameters of other functions
Address
Name
Default setting
Setting range
0x4000
Application selection
"CiA 402 advanced" technology application [1]
Selection list
PLCopen status
- (Read only)
Status word
- (Read only)
Actual position
- (Read only)
Actual velocity
- (Read only)
Actual torque
x.xx Nm (Read only)
Set position
- (Read only)
Set velocity
- (Read only)
Set torque
x.xx Nm (Read only)
Load moment of inertia
0.00 kg cm²
0.00 ... 21474836.47 kg cm²
Home position after mains switching
0
Max. angle of rotation after mains switching
0.0000000000 °
-2147483648.0000000000 ... 2147483647.0000000000 °
Default control mode
Position control via motor encoder [0]
Selection list
Actual control mode
- (Read only)
Load encoder selection
[-]
Selection list
Position controller gain
20.0000 1/s
0.0000 ... 214748.3647 1/s
Load encoder output limit
2147483647.0000000000
0.0000000000 ... 2147483647.0000000000
Position controller output
- (Read only)
Response to "hardware limit switch reached"
Fault > Application quick stop > Quick stop [19]
Selection list
SLS1
0.0000000000
0.0000000000 ... 2147483647.0000000000
SLS1 - deceleration time
0.000 s
0.000 ... 2147483.647 s
SLS2
0.0000000000
0.0000000000 ... 2147483647.0000000000
SLS2 - deceleration time
0.000 s
0.000 ... 2147483.647 s
SLS3
0.0000000000
0.0000000000 ... 2147483647.0000000000
SLS3 - deceleration time
0.000 s
0.000 ... 2147483.647 s
SLS4
0.0000000000
0.0000000000 ... 2147483647.0000000000
SLS4 - deceleration time
0.000 s
0.000 ... 2147483.647 s
Follower - Response to SLS
0
Speed controller limitation (SLS)
0
Deactivate safety interface
0x0000003E
0x00000000 ... 0xFFFFFFFF
Limiter call
- (Read only)
Status word
- (Read only)
Actual position
- (Read only)
Actual velocity
- (Read only)
Feed constant
65536.0000000000
1.0000000000 ... 2147483647.0000000000
Gearbox factor - nominator
1
1 ... 4294967295
Gearbox factor - nominator
1
1 ... 4294967295
Load encoder mounting direction
0
Max. velocity
0.0000000000
0.0000000000 ... 2147483647.0000000000
Filter cycles of actual velocity
1
1 ... 100
Filter cycles of actual position
1
1 ... 100
Home position after mains switching
0
Max. angle of rotation after mains switching
0.0000000000 °
-2147483648.0000000000 ... 2147483647.0000000000 °
Status signals
- (Read only)
Velocity actual value Motor
rpm (Read only)
Motor actual position
x incr. (Read only)
Quick stop mode
Inverter quick stop [0]
Selection list
Source of actual velocity
Motor encoder [0]
Selection list
Status Min. Velocity
25.00 %
0.00 ... 200.00 %
Action after "Home position detected"
Stop positioning [0]
Selection list
Homing: Target position
0.0000000000 incr.
-2147483648.0000000000 ... 2147483647.0000000000 incr.
Homing: Jerk
0.0000000000
0.0000000000 ... 2147483647.0000000000
Homing: Torque limit
0.0000 Nm
0.0000 ... 214748.3647 Nm
Homing: Blocking time
0.000 s
0.000 ... 2147483.647 s
Homing: Touch probe configuration
External source [0]
Selection list
Homing: Home position offset
0.0000000000 incr.
-2147483648.0000000000 ... 2147483647.0000000000 incr.
Homing mode
SetPositionDirect [0]
Selection list
Homing: Velocity for searching switch
0.0000000000
0.0000000000 ... 4294967295.0000000000
Homing: Velocity for searching 0
0.0000000000
0.0000000000 ... 4294967295.0000000000