Control commands and status information

Control commands
–
Selection of the CiA operating mode for homing:
 
–
0x6060 (CiA: Operation mode) = [6] CiA: Homing
 
 
–
Control commands for homing:
 
CiA control word
State
Function
Bit 4
0
Homing inactive.
0
↗
1
Start homing
1
↘
0
Cancel homing.
Bit12
0
↗
1
Delete reference.
 
Status information
Status information for homing:
CiA status word
State
Meaning
Bit12
0
Homing inactive or not yet completed.
1
Homing completed.
Bit 13
0
No error detected during homing.
1
An error has occurred during homing.
Extended status word
State
Meaning
Bit 2
0
Reference not known.
1
Reference known.
 
Parameter
Address
Name / setting range / [default setting]
Information
0x6040
CiA control word
0x0000 ... [0x0000] ... 0xFFFF
Mappable CiA control word with bit assignment according to device profile CiA  402.
Bit  0
Switch on
1 = switch-on
Bit  1
Enable voltage
1 = Enable voltage
Bit  2
Disable quick stop
0 = activate quick stop
Bit  3
Enable operation
1 = Enable operation
Bit  4
Operation mode specific
Bit  5
Operation mode specific
Bit  6
Operation mode specific
Bit  7
Fault reset
0-1 edge = fault reset
Bit  8
Halt
1 = stop motor (ramping down to frequency setpoint 0 Hz)
Bit  9
Operation mode specific
Operating mode specific
Bit  14
Release holding brake
1 = release holding brake
CAUTION!
–
The manually triggered "Release holding brake" command has a direct impact on the "Release holding brake [115]" trigger. Thus, the holding brake can be manually released if the power section is switched off.
 
–
The responsibility for a manual opening of the holding brake lies with the user of the external trigger source for the "Release holding brake" command.
 
Holding brake control 
Bit  15
Reserved
0x6060
CiA: Operation mode
CiA: Operation mode
-13
MS: Manual jog open loop (MOL)
Manufacturer-specific manual control
Operation mode "Manual Jog" 
-12
MS: Pole position identification (PPI)
Manufacturer-specific pole position identification (PLI)
Synchronous motor: Pole position identification (PPI) 
Selection of the PPI method for CiA mode 
0
No selection
No selection
2
CiA: Velocity mode (vl)
Operating mode "CiA 402 velocity mode (vl)" 
6
CiA: Homing
8
CiA: Cyclic sync position (csp)
Operating mode "CiA 402 cyclic sync position mode (csp)" 
9
CiA: Cyclic sync velocity mode (csv)
Operating mode "CiA 402 cyclic sync velocity mode (csv)" 
10
CiA: Cyclic sync torque mode (cst)
Operating mode "CiA 402 cyclic sync torque mode (cst)" 
0x6041
CiA status word
–
Read only
 
Mappable CiA status word with bit assignment according to device profile CiA 402.
Bit  0
Ready to switch on
1 = drive ready to start
Bit  1
Switched on
1 = drive switched-on
Bit  2
Operation enabled
1 = operation enabled
Bit  3
Fault
1 = fault or trouble active
Bit  4
Voltage enabled
1 = DC bus ready for operation
Bit  5
Quick stop disabled
0 = quick stop active
Bit  6
Switch on disabled
1 = operation inhibited
Bit  7
Warning
1 = warning active
Bit  8
RPDOs disabled
1 = cyclic PDOs have been deactivated
Bit  9
CiA control enabled
1 = inverter can receive commands via network.
–
Bit is not set in the operating mode 0x6060 = "MS: Velocity mode [-2]".
 
Bit  10
Setpoint reached
1 = the actual speed is in the window.
Bit  11
Internal limit active
1 = internal limitation of a setpoint active
Bit  12
Operation mode specific
1 = operation enabled and no test mode activated. (no internal setpoint generation active.)
Bit  13
Operation mode specific
1 ≡ following error active
Bit  14
Brake released or switching
Bit  15
STO not active
0 = STO is active or impermissible state at the safe inputs SIA and SIB (inverter disabled)
1 = STO is not active (inverter enabled)
0x282A:004
Status words: Extended status word
–
Read only
 
Bit-coded status word.
Bit  0
Brake is opened
-
Bit  1
Reserved
Bit  2
Reserved