Network configuration of the inverter with EDS file

The cyclic data transfer (Implicit Messaging) with EDS file is set up in 3 steps.
 
Preconditions
The inverter is registered with its EDS device description file in the »RSLogix™ 5000« programming software.
 
Step 1 - Set up a new Ethernet device:
1.
Go to the "Controller Organizer" under "I/O Configuration" 
à
 "Ethernet" and execute the menu command "New Module" with a right-click.
 
2.
Select the "i95A i950 Servo Drive“ module type in the dialog box.
Open the dialog "Select Module Type".
 
3.
Open tab "Catalog".
 
a.
Filter by "i9" or "lenze".
 
b.
Select the ""i95A"" catalog.
 
4.
Click "Create".
The "New Module" dialog box is opened.
 
5.
Select the dialog "General".
 
a.
Assign a name for the inverter.
 
b.
Assign an unambiguous IP address.
DNS is not supported.
The host name only describes the device.
 
 
6.
Click "Change".
 
7.
Open the "Module Definition" dialog box.
Access to the I/O data for the technology application selected and active in the inverter is defined here. See table.
Only "Exclusive Owner“ connections are supported.
The selection of the technology application in the inverter must match the selection of the technology application from the EDS file.
 
 
Connection Name
Size [Bytes]
Selected technology application in the inverter
Comment
Input
Output
Name
0x4000 =
AC Drive Profile – Basic Speed
4
4
"AC Drive Profile" technology application
5
Corresponds to the ODVA profile "AC Drive Speed/Torque"
AC Drive Profile – Extended Speed
4
4
AC Drive Profile – Basic Speed and Torque
6
6
AC Drive Profile – Extended Speed and Torque
6
6
Lenze TA Speed Control
32
32
"Speed Control" technology application
10
Lenze TA Table Positioning
32
32
"Table Positioning" technology application
20
Lenze TA Electronic Gearbox
32
32
"Electronic Gearbox" technology application
40
Lenze TA Sync and Correction
32
32
"Sync and Correction" technology application
41
Lenze TA Winder Dancer
32
32
"Winder Dancer" technology application
50
Lenze TA Winder Tension
32
32
"Winder Tension" technology application
51
Lenze TA User
1 … 64
1 … 64
"User" technology application
10000
Lenze TA Standard (generic)
32
32
Other technology applications
>1 and <100
Use selection for Lenze standard technology applications not listed in this table
 
Step 2 - Set up connection:
1.
Open the "Connection“ dialog box.
 
2.
Set "Requested Packet Interval (RPI)" (cycle with which the inverter is scanned by the scanner).
Default setting = 10 ms
For most applications, it is not necessary to scan the inverter more frequently.
Minimum value = 1 ms.
 
 
3.
Select connection type: "Unicast" or "Multicast“.
 
4.
Optional settings
 
a.
"Inhibit Module": Activate locks the inverter.
 
b.
"Major Fault On Controller If Connection Fails While in Run Mode": Activate switches the inverter to "Error" if the EtherNet/IP connection to the inverter is lost during operation.
 
5.
Click "OK".
 
6.
Assembly tags are created in the "Controller Organizer" under "Controller" 
à
 "Controller Tags".
In the sample configuration with the "LenzeServo1" inverter, these three assembly tags are generated:
"LenzeServo1:C" for the configuration assembly
"LenzeServo1:I" for the input assembly
"LenzeServo1:O" for the output assembly
Clicking the icon in front of the assembly names expands the display of the assemblies.
Since the EDS file supports "EDS Add-On Profile (AOP)", the input tags and the output tags are named application-specifically. The assignment of an alias tag is thus not necessary.
 
 
The network configuration of the inverter is now complete.
 
Step 3 - Save configuration:
1.
Save the "RSLogix™" project and load the configuration into the PLC (scanner).
Save »RSLogix™« project/Load configuration into the Scanner 
 
The configuration with the EDS file is now complete.
 
Example for an output assembly
Display of the 2 words of the output assembly "LenzeServo1:O" when using the TA Speed Control: